2017-11-28 10:19:19 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION. ANY FEEDER THAT |
| IS LESS THAN 100 AMPS IS NOT PERMITTED TO USE THE |
| DEMAND LOADS FOUND IN THE NEC AND FBC RESIDENTIAL. |
| PANEL AND FEEDERS MUST BE SIZED TO HANDLE ALL LOADS. |
| PROVIDE CORRECTION. NEC 220.82 |
| 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM, |
| SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND |
| OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE |
| AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1, |
| RE3609.3; FBC 107.2.1 |
| 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 |
| 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, |
| 225.32 |
| 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUIT. NEC 250.32; FBC RE3607.3 |
| 6. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| FBC RE3903.3 |
| 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM |
| 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE |
| OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC |
| RE3703.4 |
| 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC |
| 110.3 |
| 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12 |
| 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC CE R404.1 |
| 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 |
| AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| RE3902.12 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |