Plan Review Notes
Plan Review Notes For Permit 17100767
Permit Number 17100767
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-28 10:19:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION. ANY FEEDER THAT
 IS LESS THAN 100 AMPS IS NOT PERMITTED TO USE THE
 DEMAND LOADS FOUND IN THE NEC AND FBC RESIDENTIAL.
 PANEL AND FEEDERS MUST BE SIZED TO HANDLE ALL LOADS.
 PROVIDE CORRECTION. NEC 220.82
 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM,
 SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND
 OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE
 AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1,
 RE3609.3; FBC 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 6. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE3903.3
 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM
 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC
 RE3703.4
 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC
 110.3
 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  