Plan Review Notes For Permit 17010385 |
Permit Number |
17010385 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-25 13:06:56 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010385 | | 5/25/17 | | | | RESULTS: DENIED. | | | | 1) THE MECHANICAL PIT FOR THE HYDROWORX POOL REQUIRES | | VENTILATION PER THE SUBMITTED DESIGN AND INSTALLATION | | GUIDE (PAGE 6), AND SECTION 13 1720 OF THE PROJECT | | SPECIFICATIONS (PAGE 4, ITEM 31). PLEASE PROVIDE | | DETAILED DRAWINGS, VENTILATION CALCULATIONS, AND | | EQUIPMENT SCHEDULES AND SPECIFICATIONS. | | | | 2) PROVIDE EQUIPMENT SCHEDULES FOR THE CHILLERS | | INDICATING THE MAKES AND MODELS OF THE UNITS, THE | | COOLING CAPCITIES, THE REFRIGERANT CLASSIFICATION AND | | QUANTITIES. | | | | 3) SHOW THE CHILLED WATER PIPING RUNS AND PROVIDE | | DETAILS- TYPE AND SIZES OF CHILLED WATER PIPING, PIPE | | INSULATION TYPE AND THICKNESS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|