Plan Review Notes
Plan Review Notes For Permit 17010385
Permit Number 17010385
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-25 13:06:561ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010385
 5/25/17
  
 RESULTS: DENIED.
  
 1) THE MECHANICAL PIT FOR THE HYDROWORX POOL REQUIRES
 VENTILATION PER THE SUBMITTED DESIGN AND INSTALLATION
 GUIDE (PAGE 6), AND SECTION 13 1720 OF THE PROJECT
 SPECIFICATIONS (PAGE 4, ITEM 31). PLEASE PROVIDE
 DETAILED DRAWINGS, VENTILATION CALCULATIONS, AND
 EQUIPMENT SCHEDULES AND SPECIFICATIONS.
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR THE CHILLERS
 INDICATING THE MAKES AND MODELS OF THE UNITS, THE
 COOLING CAPCITIES, THE REFRIGERANT CLASSIFICATION AND
 QUANTITIES.
  
 3) SHOW THE CHILLED WATER PIPING RUNS AND PROVIDE
 DETAILS- TYPE AND SIZES OF CHILLED WATER PIPING, PIPE
 INSULATION TYPE AND THICKNESS.
  