Notes |
Date |
Text |
2016-12-10 07:42:31 | 1) SHT. CS.2.0 REFERS TO A REQUIRED VARIANCE FROM THE | | DEPT. OF HEALTH. IF THESE VARIANCES HAVE BEEN GRANTED, | | SUBMIT COPIES FOR REVIEW. ALSO, IF APPLICATION HAS BEEN | | MADE TO THE DEPT.OF HEALTH FOR AN OPERATING PERMIT, | | SUBMIT A COPY OF VERIFICATION THAT THE APPLICATION HAS | | BEEN RECEIVED FROM PBC DOH. 2014 FBC SEC. 454.1.1, WPB | | AMEND. TO FBC SEC. 107.2.1. | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL | | HEATER, THE NAIN DRAINS AND THE PUMPS. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 3) THE CHLORINE ROOM SHALL COMPLY WITH 2014 FBC | | SEC.454.1.6.5.16.1.1.1. | | 4) SHT. CS 5.1 - THE NON-ELECTRICAL EQUIPMENT TABLE | | CALLS OUT THE HOT SPA COLLECTOR TANK AS 690 GALLONS AND | | THE COLD SPA COLLECTOR TANK AS 460 GALLONS AND THE | | SCHEMATIC SHOWS 670 GALLONS FOR THE HOT AND 750 GALLONS | | FOR THE COLD. CLARIFY. | | 5) SHT. CS 5.2 - HAS A REFERENCE TO DETAIL "A" ON | | SHT.CP5.0. THERE IS NO SUCH SHEET IN THIS SUBMITTAL. | | CLARIFY. | | 6) THE GAS FOR THE SPA HEATERS SHALL BE A SEPARATE | | PERMIT. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|