Plan Review Notes For Permit 16111241 |
Permit Number |
16111241 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-01-09 08:41:08 | | | BUILDING PROVISO: ROOFTOP EQUIPMENT ON STANDS TO COMPLY | | WITH: | | 2014 FBC-B TABLE 1509.6.5. WHERE ROOFING MATERIALS | | EXTEND | | BENEATH THE UNIT, ON RAISED EQUIPMENT SUPORTS PROVIDING | | A | | MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE | | 1509.6.5. | | THE SUPPORTS PROVIDING CLEARANCE ARE THE HORIZONTAL | | SUPPORTS, | | THE VERTICAL DIMENSION SHOULD BE TAKEN FROM THE BOTTOM | | OF THE | | HORIZONTAL SUPPORTS TO THE FINISH ROOF DECK. IF THE | | HEATER IS | | BETWEEN 36-48 INCHES THEN THE CLEAR HEIGHT MINIMUM | | SHALL BE | | 24 INCHES HIGH. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | DEPARTMENT | | |
|