Plan Review Notes
Plan Review Notes For Permit 16100546
Permit Number 16100546
Review Stop P
Sequence Number 1
Notes
Date Text
2016-10-31 12:45:331) CLEARLY SHOW WHERE THE POOL WASTE DISCHARGES. POOL
 WATER SHALL NOT DISCHARGE TO THE CITY'S SANITARY SYSTEM
 OR TO THE STORM SYSTEM PER THE CITY OF WEST PALM BEACH
 CODE OF ORDINANCES ART.III, SEC.90-126 (B)(5) AND
 ART.V, SEC.90-203.
 2) THE EQUALIZER LINE INLET SHALL BE PROTECTED BY AN
 ASME/ANSI A112.19.8 COMPLIANT COVER/GRATE PER 2014 FBC
 SEC.454.1.6.5.3.2.3.
 3) THE FILTER RATE CAPACITY FOR THE CARTRIDGE FILTERS
 SHALL COMPLY WITH 2014 FBC SEC.454.1.6.5.5.1.
 4) PRESSURE FILTER SYSTEMS SHALL COMPLY WITH 2014 FBC
 SEC.454.1.6.5.5.2.1. SUBMIT DETAILS OF THE CARTRDGE
 FILTERS.
 5) A PORTABLE OR PLUMBED IN VACUUM CLEANING SYSTEM
 SHALL BE PROVIDED AND COMPLY WITH 2014 FBC
 SEC.454.1.6.5.12.SUBMIT DETAILS.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE POOL
 HEATERS. WPB AMEND. TO FBC SEC.107.2.1.
 7) SHT. CP4.0 - SHOW THE DISTANCE BETWEEN THE RECESSED
 TREADS FOR THE LADDER. COMPLY WITH 2014 FBC
 SEC.454.1.2.5.2.
 8) GAS FIRED POOL HEATERS SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82 PERCENT PER 2014 FBC-ENERGY, TABLE
 C404.2, SEC.C404.7.1.
 9) A TIME SWITCH OR OTHER CONTROL METHOD THAT CAN
 AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS SHALL
 BE INSTALLED ON ALL HEATERS AND PUMPS PER 2014
 FBC-ENERGY, SEC.C404.7.2.
 10) A VAPOR RETARDANT COVER ON OR AT THE SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS
 SHALL BE PROVIDED ON HEATED POOLS PER 2014 FBC-ENERGY,
 SEC.C404.7.3.
 11) EQUIPMENT ROOMS SHALL HAVE FORCED DRAFT OR CROSS
 VENTILATION IN ACCORDANCE WITH 2014 FBC SEC.454.1.5.4.
 12) A SEPARATE PERMIT IS REQUIRED FOR THE GAS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  