2016-03-08 08:59:02 | 1) SHT.C9.21 - GREASE/WATER SEPARATOR DETAIL - THE CITY |
| DETAIL ON THE PLAN IS AN OUTDATED DETAIL. REFER TO |
| DETAIL GS 7 ISSUED IN 2015. |
| 2) SHT. IR1.07 - SUBMIT COMPLETE DETAILS FOR THE ACID |
| INJECTION SYSTEM FOR THE IRRIGATION SYSTEM, CONTAINMENT |
| SYSTEM, PUMPS, VALVES, PIPING, ETC. FBC 107.2.1. SHOW |
| HOW THIS AREA WILL BE PROTECTED AGAINST UNAUTHORIZED |
| ENTRY. |
| 3) SUBMIT MSDS DATA FOR THE CHEMICALS USED FOR THE ACID |
| INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.FBC 107.2.1. |
| 4) SHT. A1.22 - DETAIL #2 - THE GUTTERS FOR THE BATTING |
| TUNNEL ROOF SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| 1106.6 OF THE 2014 FL. PLUMBING CODE. CLEARLY THE |
| LOCATION OF ALL GUTTERS ON THE PLAN. |
| 5) THE ROOM FINISH PLAN ON SHT. A3.40 SHOWS THE WALLS |
| IN SOME OF THE RESTROOMS AND TOILET ROOMS AS PAINT. |
| 2014 FBC SEC. 1210.2.2 REQUIRES WALLS AND PARTITIONS |
| WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER |
| CLOSETS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO |
| A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| FLOOR.EXCEPTION:TOILET ROOMS THAT ARE NOT ACCESSIBLE TO |
| THE PUBLIC AND WHICH HAVE NOT MORE THAN ONE WATER |
| CLOSET. |
| 6) SINKS LOCATED IN BREAK ROOM AREAS SHALL COMPLY WITH |
| THE 2014 FAC SEC.212 & 606. |
| 7) THE LAUNDRY AREAS SHALL COMPLY WITH THE 2014 FAC |
| SEC.611. |
| 8) SHT. A2.913 - DETAIL # 01 - THE WATER CLOSET SHALL |
| BE LOCATED DIAGONALLY OF THE COMPARTMENT DOOR PER 2014 |
| FAC SEC.604.8.1.2. |
| 9) SHT. A2.914 - DETAILS # 3 & #4 - THE DOOR SHALL BE |
| LOCATED PER FAC SEC.604.8.1.2. |
| 10) SHT.A3.23 - DETAIL EWC 3 - THE SPOUT ON THE HIGH |
| SIDE DRINKING FOUNTAIN SHALL BE LOCATED 38-43 INCHES |
| ABOVE THE FINISH FLOOR OR GROUND PER THE FAC SEC.602.7. |
| 11) SHT.A#.23 - ACCESSIBLE ROLL IN SHOWER WITH GRAB BAR |
| AND SEAT - THIS IS CONSIDERED AN ALTERNATE ROLL- IN |
| TYPE SHOWER DUE TO THE SIZE (36" X 60") AND THE |
| LOCATION OF THE SHOWER SEAT SHALL COMPLY WITH THE 2014 |
| FAC SEC.610.3 AND THE LOCATION OF THE CONTROLS SHALL |
| COMPLY WITH SEC.608.5.3. |
| 12) SHT. A3.23 - ACCESSIBLE SHOWER TRANSFER - THE |
| CONTROLS SHALL BE A MINIMUM OF 38 INCHES AND A MAXIMUM |
| OF 48 INCHES ABOVE THE SHOWER FLOOR AND SHALL BE |
| LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM THE |
| CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. FAC |
| SEC.608.5.1. |
| 13) TOILET PAPER DISPENSERS IN THE ACCESSIBLE TOILET |
| ROOMS/COMPARTMENTS SHALL BE LOCATED A MINIMUM OF 7 |
| INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER |
| CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. FAC |
| SEC.604.7. |
| 14) SHT. A8.21 - ALL NEWLY INSTALLED UNDERGROUND |
| HYDRAULIC PRESSURE CYLINDERS SHALL BE ENCASED IN OUTER |
| PLASTIC CONTAINMENT TO MINIMIZE ELECTROLYTIC CORROSION |
| BETWEEN THE METAL CYLINDER AND GROUND CATHODE. 2014 FBC |
| SEC.3011.1. |
| 15) SHT. P0.03 - THE PLUMBING FIXTURE SCHEDULE SHOWS |
| LAVATORY FAUCETS 2B & 2C WITH COLD WATER ONLY. HOT OR |
| TEMPERED SHALL BE SUPPLIED TO THE LAVATORIES PER FPC |
| SEC.607.1.THE WATER RISERS SHALL CLEARLY SHOW |
| HOT/TEMPERED WATER TO THE REQUIRED FIXTURES. |
| 16) SHT. P2.001, 002 & 003 - THE OVERALL PLANS ARE |
| PEPPERED WITH DARK MARKS AND ARE IMPOSSIBLE TO SEE WHAT |
| THEY REPRESENT. CLARIFY. |
| 17) SHT. P2.114 - THERE IS A GREASY WASTE LINE THAT |
| APPEARS TO BE ALSO LABELED AS A SANITARY LINE.SEE AREA |
| BETWEEN GRID LINES S17 & S18 AND SG & SH. PLEASE CHECK |
| ALL SHEETS TO ENSURE THE DRAINAGE LINES ARE PROPERLY |
| LABELED. |
| 18) SHT.P4.003 - APPROVAL IS REQUIRED FROM THE PALM |
| BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCE PROTECTION |
| FOR THE ABOVE GROUND FUEL STORAGE TANKS. PBC ORD. # |
| 2015 - 008. |
| 19) SHT. P4.003 - THE FUELING SCHEMATIC REFERS TO |
| SEVERAL DETAILS ( A,B,C, ETC.) WHERE ARE THESE DETAILS? |
| CLARIFY. |
| 20) SHT.P4.003 - NUMBERED NOTE #1 REFERS TO A ONE |
| THOUSAND GALLON DIVIDED FUEL TANK BUT THE FUELING |
| SYSTEM SCHEMATIC SHOWS A DIVIDED 2500 GALLON TANK. |
| CLARIFY. |
| 21) THE SANITARY AND WATER RISERS ARE INCOMPLETE AND |
| DEFICIENT AND A THOROUGH AND COMPREHENSIVE REVIEW COULD |
| NOT BE DONE AT THIS TIME. AS-BUILT SANITARY AND WATER |
| RISERS WILL BE SUBMITTED DURING THE INSPECTION PROCESS. |
| 22) PLACE THE ROOM NUMBERS ON THE ENLARGED PLANS. IT IS |
| DIFFICULT TO LOCATE THESE AREAS ON THE PLAN VIEW |
| LAYOUT. FBC 107.2.1. |
| 23) SAMPLING PORTS ARE REQUIRED ON THE DISCHARGE SIDE |
| OF EACH GREASE INTERCEPTOR PER THE CWPB STANDARD |
| DRAWING GS-7.1. |
| 24) SUBMIT MANUF. SPECIFICATIONS FOR THE RETROCEPTOR |
| SHOWN IN THE STADIUM SUITE LEVEL PARTY DECK. |
| 25) SHT. S5.101.5 - THERE ARE NUMBERED NOTE TAGS ON THE |
| RISER DIAGRAM BUT THERE ARE NO NUMBERED NOTES ON THE |
| DRAWING. CLARIFY. |
| 26) SHT.P5.401 - THE SHEET DRAWING NUMBERS THAT SHOW |
| THE CONTINUATION OF THE FUEL GAS SYSTEM ARE ILLEGIBLE . |
| SUBMIT A PLAN THAT CLEARLY SHOWS THE SHEET DRAWING |
| NUMBERS. FBC 107.2.1. |
| 27) CLEARLY SHOW THE LOCATION OF ALL MEDIUM PRESSURE |
| GAS REGULATORS ON THE GAS RISERS. FBC 107.2.1. |
| 28) CLEARLY SHOW THE PIPE SIZES OF THE PIPING |
| DOWNSTREAM OF THE MP REGULATOR.FBC 107.2.1. |
| 29) SIZE ALL SECTIONS OF THE PIPING ON ALL GAS |
| RISERS.FBC 107.2.1. |
| 30) IDENTIFY THE GAS METER ON THE GAS RISER ON |
| SHT.P5.401. |
| 31) IDENTIFY EACH PIECE OF GAS EQUIPMENT ON THE GAS |
| RISER AND THE BTU LOAD FOR EACH PICE OF |
| EQUIPMENT/APPLIANCE.FBC 107.2.1. |
| 31) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| FBC-FUEL GAS CODE SEC.304.1. |
| 32) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| SECS. 502 THRU 505. |
| 33) ALL EQUIPMENT SHALL BE LISTED AND LABELED IN |
| ACCORDANCE WITH 2014 FGC SEC.301.3. |
| 34) SHT. P5.401 - MEP EQUIPMENT SCHEDULE SHOWS THE |
| GWH-2 AS 1950 MBH BUT SHEET P5.401.1 APPEARS TO SHOW |
| GWH-2 WITH LESS BTU'S. CLARIFY. |
| 35) SHT. P5.401.3 - SUBMIT AN EXPANDED GAS RISER |
| DIAGRAM FOR THE WATER HEATERS AND SHOW THE REGULATOR. |
| IT IS IMPOSSIBLE TO SEE WHERE THE MEDIUM PRESSURE AND |
| LOW PRESSURE PIPING BEGINS AND ENDS. |
| 36) THE FOLLOWING COMMENTS ARE ALL FOR SHT. P5.402 - |
| THE 2" MEP LINE IS UNDERSIZED.TABLE 402.4 (5) LIMITS A |
| 2' LINE TO 2010MBH.THE DRAWING SHOWS A BTU LOAD FROM |
| 2010 MBH UP TO 3030 MBH. |
| 37) THE 1 1/4 " LINE WITH 700MBH IS UNDERSIZED.MAXIMUM |
| ALLOWED BY TABLE 402.4 (5) IS 695 MBH. THE LINE SHALL |
| BE 1 1/2" MINIMUM. |
| 38) THE 1" MEDIUM PRESSURE LINE WITH 440 MBH IS |
| UNDERSIZED. MAXIMUM IS 339MBH.THE LINE SHALL BE 1 1/4". |
| 39) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1640MBH |
| NEEDS TO BE 2" PER TABLE 402.4 (5). |
| 40) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1440 MBH |
| NEEDS TO BE 2". |
| 41) THE 1"MP LINE CARRYING 440 MBH NEEDS TO BE 1 1/4". |
| 42) SHT. P5.402.1 - THE FOLLOWING COMMENTS ARE ALL |
| APPLICABLE TO SHT.P5.402.1. |
| 43) THE 1 1/4" MP LINE CARRYING 700 MBH IS UNDERSIZED. |
| IT NEEDS TO BE 1 1/2". |
| 44) THE 1" MP & LOW PRESSURE LINE CARRYING 440 MBH IS |
| UNDERSIZED. BOTH LINES NEED TO BE 1 1/4". |
| 45) THE 3/4" MP LINE CARRYING 300 MBH IS UNDERSIZED. IT |
| NEEDS TO BE 1". THE LOW PRESSURE SAID NEEDS TO BE 1 |
| 1/4". |
| 46) THE 1 1/2" MP LINE CARRYING 1440 MBH IS UNDERSIZED. |
| IT NEEDS TO BE 2". TABLE 402.4 (5). |
| 47) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED. |
| IT NEEDS TO BE 2". TABLE 402.4 (5). |
| 48)SHT. P5.402.2. - THE FOLLOWING COMMENTS ARE ALL |
| APPLICABLE TO SHT. P5.402.2. - |
| 49) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED. |
| IT NEEDS TO BE 2". |
| 50) THE 2" MP LINE CARRYING 2080MBH IS UNDERSIZED. IT |
| NEEDS TO BE 2 1/2". TABLE 402.4 (5). |
| 51) THE 1" MP LINE CARRYING 440MBH IS UNDERSIZED. IT |
| NEEDS TO BE 1 1/4". |
| 52) THE 2" MP LINE CARRYING 2130 IS UNDERSIZED. IT |
| NEEDS TO BE 2 1/2". |
| 53) THE 1 1/4" LOW PRESSURE LINE CARRYING 700MBH IS |
| UNDERSIZED. IT NEEDS TO BE 1 1/2". |
| 54) THE 2" MP LINE CARRYING 3030MBH IS UNDERSIZED.IT |
| NEEDS TO BE 2 1/2". |
| 55) THE 3" MP LINE CARRYING 6930MBH IS UNDERSIZED. IT |
| NEEDS TO BE 4". |
| 56) THE 2 1/2" MP LINE CARRYING 3900 IS UNDERSIZED. IT |
| NEEDS TO BE 3". |
| 57) THE 2" LOW PRESSURE LINE CARRYING 1950MBH IS |
| UNDERSIZED. IT NEEDS TO BE 2 1/2'. |
| 58) THE FOLLOWING COMMENTS ARE ALL APPLICABLE TO |
| SHT.P5.403. |
| 59) PROVIDE THE TEXT FOR NUMBERED NOTE #1. |
| 60) THE 1" MP LINE CARRYING 500MBH IS UNDERSIZED. IT |
| NEEDS TO BE 1 1/4". |
| 61) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED. |
| IT NEEDS TO BE 2". |
| 62) THE 1 1/4"MP LINE CARRYING 700MBH IS UNDERSIZED. IT |
| NEEDS TO BE 1 1/2". |
| 63) THE 2" MP LINE CARRYING 2020MBH, 2220MBH, AND 2320 |
| MBH IS UNDERSIZED. IT NEEDS TO BE 2 1/2". |
| 64) THE 3/4" MP LINE CARRYING 200MBH IS UNDERSIZED. IT |
| NEEDS TO BE 1". |
| 65) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED. |
| IT NEEDS TO BE 2". |
| 66) THE 3" MP LINE CARRYING 6970 MBH IS UNDERSIZED. IT |
| NEEDS TO BE 4". |
| 67) THE 2 1/2" MP LINE CARRYING 3900MBH IS UNDERSIZED. |
| IT NEEDS TO BE 3". |
| 68) SHT.P5.403.1 - CHECK THE ENTIRE RISER FOR CORRECT |
| SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND |
| 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD. |
| 69) SHT. P5.403.2 - CHECK THE ENTIRE RISER FOR CORRECT |
| SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND |
| 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD. |
| 70) SHT.P4.003 - SUBMIT A LEGEND FOR ALL THE COMPONENT |
| TAGS THAT ARE SHOWN ON THE PLAN. FBC 107.2.1. |
| 71) INDICATE THE LIQUID CLASS FOR THE GASOLINE ON THE |
| PLANS IN ACCORDANCE WITH CHAPT.2 OF 2014 FBC. |
| 72) MANUFACTURER'S SPECIFICATIONS FOR DISPENSERS, |
| TANKS, VALVES, ETC. SHALL BE SUBMITTED FOR REVIEW. THE |
| DOCUMENTS CAN BE SUBMITTED NOW OR BE A DEFERRED |
| SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.2. |
| 73) DEFINE THE OCCUPANCY FOR THIS STRUCTURE. THE AMOUNT |
| OF COMBUSTIBLE/FLAMMABLE LIQUID STORAGE APPEARS TO |
| DEFINE THIS STRUCTURE AS AN "H" OCCUPANCY PER CHAPT. |
| 307.4, 307.5 & CHAPT. 4 OF THE 2014 FBC. |
| 74) THE TANKS,DISPENSERS AND ALL ASSOCIATED PIPING AND |
| CONSTRUCTION OF THE ENCLOSURE SHALL COMPLY WITH NFPA 30 |
| AND 2014 FBC. |
| 75) SUBMIT A CONDENSATE RISER FOR REVIEW. THE |
| CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY PER CITY |
| ORDINANCE OR TO THE GREASY WASTE SYSTEM. 2014 FBC SEC. |
| 1003.2. |
| |