Plan Review Notes
Plan Review Notes For Permit 16020418
Permit Number 16020418
Review Stop P
Sequence Number 1
Notes
Date Text
2016-03-08 08:59:021) SHT.C9.21 - GREASE/WATER SEPARATOR DETAIL - THE CITY
 DETAIL ON THE PLAN IS AN OUTDATED DETAIL. REFER TO
 DETAIL GS 7 ISSUED IN 2015.
 2) SHT. IR1.07 - SUBMIT COMPLETE DETAILS FOR THE ACID
 INJECTION SYSTEM FOR THE IRRIGATION SYSTEM, CONTAINMENT
 SYSTEM, PUMPS, VALVES, PIPING, ETC. FBC 107.2.1. SHOW
 HOW THIS AREA WILL BE PROTECTED AGAINST UNAUTHORIZED
 ENTRY.
 3) SUBMIT MSDS DATA FOR THE CHEMICALS USED FOR THE ACID
 INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.FBC 107.2.1.
 4) SHT. A1.22 - DETAIL #2 - THE GUTTERS FOR THE BATTING
 TUNNEL ROOF SHALL BE SIZED IN ACCORDANCE WITH TABLE
 1106.6 OF THE 2014 FL. PLUMBING CODE. CLEARLY THE
 LOCATION OF ALL GUTTERS ON THE PLAN.
 5) THE ROOM FINISH PLAN ON SHT. A3.40 SHOWS THE WALLS
 IN SOME OF THE RESTROOMS AND TOILET ROOMS AS PAINT.
 2014 FBC SEC. 1210.2.2 REQUIRES WALLS AND PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER
 CLOSETS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO
 A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR.EXCEPTION:TOILET ROOMS THAT ARE NOT ACCESSIBLE TO
 THE PUBLIC AND WHICH HAVE NOT MORE THAN ONE WATER
 CLOSET.
 6) SINKS LOCATED IN BREAK ROOM AREAS SHALL COMPLY WITH
 THE 2014 FAC SEC.212 & 606.
 7) THE LAUNDRY AREAS SHALL COMPLY WITH THE 2014 FAC
 SEC.611.
 8) SHT. A2.913 - DETAIL # 01 - THE WATER CLOSET SHALL
 BE LOCATED DIAGONALLY OF THE COMPARTMENT DOOR PER 2014
 FAC SEC.604.8.1.2.
 9) SHT. A2.914 - DETAILS # 3 & #4 - THE DOOR SHALL BE
 LOCATED PER FAC SEC.604.8.1.2.
 10) SHT.A3.23 - DETAIL EWC 3 - THE SPOUT ON THE HIGH
 SIDE DRINKING FOUNTAIN SHALL BE LOCATED 38-43 INCHES
 ABOVE THE FINISH FLOOR OR GROUND PER THE FAC SEC.602.7.
 11) SHT.A#.23 - ACCESSIBLE ROLL IN SHOWER WITH GRAB BAR
 AND SEAT - THIS IS CONSIDERED AN ALTERNATE ROLL- IN
 TYPE SHOWER DUE TO THE SIZE (36" X 60") AND THE
 LOCATION OF THE SHOWER SEAT SHALL COMPLY WITH THE 2014
 FAC SEC.610.3 AND THE LOCATION OF THE CONTROLS SHALL
 COMPLY WITH SEC.608.5.3.
 12) SHT. A3.23 - ACCESSIBLE SHOWER TRANSFER - THE
 CONTROLS SHALL BE A MINIMUM OF 38 INCHES AND A MAXIMUM
 OF 48 INCHES ABOVE THE SHOWER FLOOR AND SHALL BE
 LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. FAC
 SEC.608.5.1.
 13) TOILET PAPER DISPENSERS IN THE ACCESSIBLE TOILET
 ROOMS/COMPARTMENTS SHALL BE LOCATED A MINIMUM OF 7
 INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. FAC
 SEC.604.7.
 14) SHT. A8.21 - ALL NEWLY INSTALLED UNDERGROUND
 HYDRAULIC PRESSURE CYLINDERS SHALL BE ENCASED IN OUTER
 PLASTIC CONTAINMENT TO MINIMIZE ELECTROLYTIC CORROSION
 BETWEEN THE METAL CYLINDER AND GROUND CATHODE. 2014 FBC
 SEC.3011.1.
 15) SHT. P0.03 - THE PLUMBING FIXTURE SCHEDULE SHOWS
 LAVATORY FAUCETS 2B & 2C WITH COLD WATER ONLY. HOT OR
 TEMPERED SHALL BE SUPPLIED TO THE LAVATORIES PER FPC
 SEC.607.1.THE WATER RISERS SHALL CLEARLY SHOW
 HOT/TEMPERED WATER TO THE REQUIRED FIXTURES.
 16) SHT. P2.001, 002 & 003 - THE OVERALL PLANS ARE
 PEPPERED WITH DARK MARKS AND ARE IMPOSSIBLE TO SEE WHAT
 THEY REPRESENT. CLARIFY.
 17) SHT. P2.114 - THERE IS A GREASY WASTE LINE THAT
 APPEARS TO BE ALSO LABELED AS A SANITARY LINE.SEE AREA
 BETWEEN GRID LINES S17 & S18 AND SG & SH. PLEASE CHECK
 ALL SHEETS TO ENSURE THE DRAINAGE LINES ARE PROPERLY
 LABELED.
 18) SHT.P4.003 - APPROVAL IS REQUIRED FROM THE PALM
 BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCE PROTECTION
 FOR THE ABOVE GROUND FUEL STORAGE TANKS. PBC ORD. #
 2015 - 008.
 19) SHT. P4.003 - THE FUELING SCHEMATIC REFERS TO
 SEVERAL DETAILS ( A,B,C, ETC.) WHERE ARE THESE DETAILS?
 CLARIFY.
 20) SHT.P4.003 - NUMBERED NOTE #1 REFERS TO A ONE
 THOUSAND GALLON DIVIDED FUEL TANK BUT THE FUELING
 SYSTEM SCHEMATIC SHOWS A DIVIDED 2500 GALLON TANK.
 CLARIFY.
 21) THE SANITARY AND WATER RISERS ARE INCOMPLETE AND
 DEFICIENT AND A THOROUGH AND COMPREHENSIVE REVIEW COULD
 NOT BE DONE AT THIS TIME. AS-BUILT SANITARY AND WATER
 RISERS WILL BE SUBMITTED DURING THE INSPECTION PROCESS.
 22) PLACE THE ROOM NUMBERS ON THE ENLARGED PLANS. IT IS
 DIFFICULT TO LOCATE THESE AREAS ON THE PLAN VIEW
 LAYOUT. FBC 107.2.1.
 23) SAMPLING PORTS ARE REQUIRED ON THE DISCHARGE SIDE
 OF EACH GREASE INTERCEPTOR PER THE CWPB STANDARD
 DRAWING GS-7.1.
 24) SUBMIT MANUF. SPECIFICATIONS FOR THE RETROCEPTOR
 SHOWN IN THE STADIUM SUITE LEVEL PARTY DECK.
 25) SHT. S5.101.5 - THERE ARE NUMBERED NOTE TAGS ON THE
 RISER DIAGRAM BUT THERE ARE NO NUMBERED NOTES ON THE
 DRAWING. CLARIFY.
 26) SHT.P5.401 - THE SHEET DRAWING NUMBERS THAT SHOW
 THE CONTINUATION OF THE FUEL GAS SYSTEM ARE ILLEGIBLE .
 SUBMIT A PLAN THAT CLEARLY SHOWS THE SHEET DRAWING
 NUMBERS. FBC 107.2.1.
 27) CLEARLY SHOW THE LOCATION OF ALL MEDIUM PRESSURE
 GAS REGULATORS ON THE GAS RISERS. FBC 107.2.1.
 28) CLEARLY SHOW THE PIPE SIZES OF THE PIPING
 DOWNSTREAM OF THE MP REGULATOR.FBC 107.2.1.
 29) SIZE ALL SECTIONS OF THE PIPING ON ALL GAS
 RISERS.FBC 107.2.1.
 30) IDENTIFY THE GAS METER ON THE GAS RISER ON
 SHT.P5.401.
 31) IDENTIFY EACH PIECE OF GAS EQUIPMENT ON THE GAS
 RISER AND THE BTU LOAD FOR EACH PICE OF
 EQUIPMENT/APPLIANCE.FBC 107.2.1.
 31) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1.
 32) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505.
 33) ALL EQUIPMENT SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH 2014 FGC SEC.301.3.
 34) SHT. P5.401 - MEP EQUIPMENT SCHEDULE SHOWS THE
 GWH-2 AS 1950 MBH BUT SHEET P5.401.1 APPEARS TO SHOW
 GWH-2 WITH LESS BTU'S. CLARIFY.
 35) SHT. P5.401.3 - SUBMIT AN EXPANDED GAS RISER
 DIAGRAM FOR THE WATER HEATERS AND SHOW THE REGULATOR.
 IT IS IMPOSSIBLE TO SEE WHERE THE MEDIUM PRESSURE AND
 LOW PRESSURE PIPING BEGINS AND ENDS.
 36) THE FOLLOWING COMMENTS ARE ALL FOR SHT. P5.402 -
 THE 2" MEP LINE IS UNDERSIZED.TABLE 402.4 (5) LIMITS A
 2' LINE TO 2010MBH.THE DRAWING SHOWS A BTU LOAD FROM
 2010 MBH UP TO 3030 MBH.
 37) THE 1 1/4 " LINE WITH 700MBH IS UNDERSIZED.MAXIMUM
 ALLOWED BY TABLE 402.4 (5) IS 695 MBH. THE LINE SHALL
 BE 1 1/2" MINIMUM.
 38) THE 1" MEDIUM PRESSURE LINE WITH 440 MBH IS
 UNDERSIZED. MAXIMUM IS 339MBH.THE LINE SHALL BE 1 1/4".
 39) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1640MBH
 NEEDS TO BE 2" PER TABLE 402.4 (5).
 40) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1440 MBH
 NEEDS TO BE 2".
 41) THE 1"MP LINE CARRYING 440 MBH NEEDS TO BE 1 1/4".
 42) SHT. P5.402.1 - THE FOLLOWING COMMENTS ARE ALL
 APPLICABLE TO SHT.P5.402.1.
 43) THE 1 1/4" MP LINE CARRYING 700 MBH IS UNDERSIZED.
 IT NEEDS TO BE 1 1/2".
 44) THE 1" MP & LOW PRESSURE LINE CARRYING 440 MBH IS
 UNDERSIZED. BOTH LINES NEED TO BE 1 1/4".
 45) THE 3/4" MP LINE CARRYING 300 MBH IS UNDERSIZED. IT
 NEEDS TO BE 1". THE LOW PRESSURE SAID NEEDS TO BE 1
 1/4".
 46) THE 1 1/2" MP LINE CARRYING 1440 MBH IS UNDERSIZED.
 IT NEEDS TO BE 2". TABLE 402.4 (5).
 47) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED.
 IT NEEDS TO BE 2". TABLE 402.4 (5).
 48)SHT. P5.402.2. - THE FOLLOWING COMMENTS ARE ALL
 APPLICABLE TO SHT. P5.402.2. -
 49) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED.
 IT NEEDS TO BE 2".
 50) THE 2" MP LINE CARRYING 2080MBH IS UNDERSIZED. IT
 NEEDS TO BE 2 1/2". TABLE 402.4 (5).
 51) THE 1" MP LINE CARRYING 440MBH IS UNDERSIZED. IT
 NEEDS TO BE 1 1/4".
 52) THE 2" MP LINE CARRYING 2130 IS UNDERSIZED. IT
 NEEDS TO BE 2 1/2".
 53) THE 1 1/4" LOW PRESSURE LINE CARRYING 700MBH IS
 UNDERSIZED. IT NEEDS TO BE 1 1/2".
 54) THE 2" MP LINE CARRYING 3030MBH IS UNDERSIZED.IT
 NEEDS TO BE 2 1/2".
 55) THE 3" MP LINE CARRYING 6930MBH IS UNDERSIZED. IT
 NEEDS TO BE 4".
 56) THE 2 1/2" MP LINE CARRYING 3900 IS UNDERSIZED. IT
 NEEDS TO BE 3".
 57) THE 2" LOW PRESSURE LINE CARRYING 1950MBH IS
 UNDERSIZED. IT NEEDS TO BE 2 1/2'.
 58) THE FOLLOWING COMMENTS ARE ALL APPLICABLE TO
 SHT.P5.403.
 59) PROVIDE THE TEXT FOR NUMBERED NOTE #1.
 60) THE 1" MP LINE CARRYING 500MBH IS UNDERSIZED. IT
 NEEDS TO BE 1 1/4".
 61) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED.
 IT NEEDS TO BE 2".
 62) THE 1 1/4"MP LINE CARRYING 700MBH IS UNDERSIZED. IT
 NEEDS TO BE 1 1/2".
 63) THE 2" MP LINE CARRYING 2020MBH, 2220MBH, AND 2320
 MBH IS UNDERSIZED. IT NEEDS TO BE 2 1/2".
 64) THE 3/4" MP LINE CARRYING 200MBH IS UNDERSIZED. IT
 NEEDS TO BE 1".
 65) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED.
 IT NEEDS TO BE 2".
 66) THE 3" MP LINE CARRYING 6970 MBH IS UNDERSIZED. IT
 NEEDS TO BE 4".
 67) THE 2 1/2" MP LINE CARRYING 3900MBH IS UNDERSIZED.
 IT NEEDS TO BE 3".
 68) SHT.P5.403.1 - CHECK THE ENTIRE RISER FOR CORRECT
 SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND
 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD.
 69) SHT. P5.403.2 - CHECK THE ENTIRE RISER FOR CORRECT
 SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND
 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD.
 70) SHT.P4.003 - SUBMIT A LEGEND FOR ALL THE COMPONENT
 TAGS THAT ARE SHOWN ON THE PLAN. FBC 107.2.1.
 71) INDICATE THE LIQUID CLASS FOR THE GASOLINE ON THE
 PLANS IN ACCORDANCE WITH CHAPT.2 OF 2014 FBC.
 72) MANUFACTURER'S SPECIFICATIONS FOR DISPENSERS,
 TANKS, VALVES, ETC. SHALL BE SUBMITTED FOR REVIEW. THE
 DOCUMENTS CAN BE SUBMITTED NOW OR BE A DEFERRED
 SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.2.
 73) DEFINE THE OCCUPANCY FOR THIS STRUCTURE. THE AMOUNT
 OF COMBUSTIBLE/FLAMMABLE LIQUID STORAGE APPEARS TO
 DEFINE THIS STRUCTURE AS AN "H" OCCUPANCY PER CHAPT.
 307.4, 307.5 & CHAPT. 4 OF THE 2014 FBC.
 74) THE TANKS,DISPENSERS AND ALL ASSOCIATED PIPING AND
 CONSTRUCTION OF THE ENCLOSURE SHALL COMPLY WITH NFPA 30
 AND 2014 FBC.
 75) SUBMIT A CONDENSATE RISER FOR REVIEW. THE
 CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY PER CITY
 ORDINANCE OR TO THE GREASY WASTE SYSTEM. 2014 FBC SEC.
 1003.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692