2016-09-08 11:03:025211 NORTH MILITARY - OBSERVATION TOWER
 PERMIT #15100826
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENTS: THE EXTERIOR STAIR IS REQUIRED TO BE
 SEPARATED FROM THE INTERIOR OF THE BUILDING WITH A
 1-HOUR FIRE BARRIER AND PROTECTED OPENINGS PER NFPA 101
 SECTION 7.2.2.6.3.1. THE STAIRS DISCHARGE BEYOND THE
 FACE OF THE BUILDING AND REQUIRE THE 1-HOUR FIRE
 BARRIER TO EXTEND 10-FEET HORIZONTALLY FROM THE STAIR.
 THIS WILL REQUIRE THE DOORS TO BE FIRE RATED AND THE
 LOUVERS TO BE PROTECTED WITH FIRE DAMPERS.
  
 REPEAT COMMENT: HAZARD SEPARATION: FIELD STORAGE #02803
 NEEDS TO BE FIRE SEPARATED FROM THE BUSINESS OCCUPANCY
 WITH EITHER 1-HOUR FIRE BARRIER OR FIRE SPRINKLERS PER
 NFPA 101 SECTION 38.3.2 PROTECTION FROM HAZARDS.
 HAZARDOUS AREAS INCLUDING, BUT NOT LIMITED TO, AREAS
 USED FOR GENERAL STORAGE, BOILER OR FURNACE ROOMS, AND
 MAINTENANCE SHOPS THAT INCLUDE WOODWORKING AND PAINTING
 AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 8.7. THIS IS A HAZARD SEPARATION AND NOT AN OCCUPANCY
 SEPARATION, WHICH WOULD REQUIRE A 2-HOUR FIRE BARRIER.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE