Plan Review Notes For Permit 14120915 |
Permit Number |
14120915 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2015-10-08 11:36:22 | ELECTRICAL PROVISO FOR PERMIT 14120915 | | IN ORDER TO BRING THE UNPERMITTED KITCHEN INTO | | COMPLIANCE, THE MINIMUM REQUIRED OUTLETS SHALL BE IN | | PLACE. THE DRAWING SUBMITTED FAILS TO INDICATE; | | THEREFORE CORRECTIONS ARE REQUIRED. FURTHERMORE THE | | PANEL PERMITTED OR NOT SHALL ALSO BE ACCORDING TO | | MINIMUM CODE STANDARDS; THUS REQUIRING THAT THERE BE A | | DISCONNECT AS INDICATED BY NEC 230.70(A)(1). SEE NEC | | 230.6 FOR FURTHER DETAILS. | | |
|