Plan Review Notes
Plan Review Notes For Permit 14120915
Permit Number 14120915
Review Stop E
Sequence Number 4
Notes
Date Text
2015-03-31 14:16:153/31/2015
 PROJECT: LJUBO 827 BRIGGS ST
 PERMIT#: 14100826
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE ELECTRICAL RISER DIAGRAM TO INDICATE THE
 FOLLOWING:
 A MAIN DISCONNECTING MEANS AS REQUIRED BY NEC 230.70
 SIZES OF MAIN DISCONNECT, SERVICE ENTRANCE, FEEDERS,
 PANEL, AND GROUNDING ELECTRODE SYSTEM. NEC 215.5,
 250.50
  
 2) LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN
 PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN
 ACCORDANCE WITH EITHER 220.12 OR 220.14, AS APPLICABLE.
 NEC 220.16(2)
  
 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) INDICATE CIRCUITS ON THE FLOORPLAN FOR CLARITY. WPB
 AMENDMENTS TO FBC 107.3.2
  
 4) AT LEAST ONE GFI RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH PENINSULAR COUNTERTOP SPACE. NEC
 210.52(C)(3)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]