2013-08-21 11:59:27 | BUILDING PLAN REVIEW |
| PERMIT: 13070610 |
| ADD: 720 S SAPODILLA AV- ROOFTOP |
| CONT: HAYDEN PROFESSIONAL SERVICES |
| TEL: (772)781-1512 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: 8/ 21/2012 |
| ACTION: DENIED |
| |
| 1) COMPLIED. PLANS BEING SUBMITTED FOR CITY REVIEW |
| REQUIRES CITY PLACE STAMP OF REVIEW AND APPROVAL. |
| |
| 2) 2ND REVIEW. SUBMITTED IS A PRE-MANUFACTURED |
| BUILDING, IT APPEARS NOT TO BE A STATE APPROVED PLAN, |
| SINCE THERE IS ONLY AN APPROVAL FROM PFS AND ONLY ON A |
| FEW SHEETS,NOR IS THE SIGNATURE OF THE PLANS EXAMINER |
| LICENSE NUMBER FOUND ON THE DBPR WEBSITE. THE |
| ENGINEERING PROVIDED BY JOHN IRVING P. E. DOES INDICATE |
| THIS STRUCTURE TO BE ELEVATED SINCE THERE IS A HEIGHT |
| ADJUSTMENT FACTOR OF 1.62. THE ISSUE IS THIS MODULAR |
| BUILDING IS GOING TO BE LOCATED ON TOP OF AN EXISTING 5 |
| STORY III-A FULLY SPRINKLERED BUILDING. AS INDICATED |
| PAGE 1 OF 15 BUILDING TYPE V-B AND BUILDING LIMITATIONS |
| 1.3.3 OCCUPANCY S-2 OR B OR U FROM THE 2010 FBC-TABLE |
| 503THIS STRUCTURE CAN NOT BE PLACED ANY HIGHER THAN 2 |
| STORIES. |
| THE ORIGINAL BUILDING BEING BUILT AS A MIXED USE |
| MERCANTILE 1ST FLOOR AND R2 THE SECOND THRU 5TH FLOOR |
| WHICH ALLOWED FOR 4 STORIES, IT IS FULLY SPRINKLERED |
| WITH A FULL NFPA 13 SPRINKLER THAT GACE THEM A ONE |
| STORY INCREASE, THE NEW MODULAR STRUCTURE WOULD ALSO BE |
| REQUIRED TO BE FULLY SPRINKLERED AND A MINIMUM BUILDING |
| TYPE OF IIIA. |
| |
| 3) 2ND REQUEST.SHEET S2 DETAIL # 5 INDICATES A SPECIAL |
| PLATE DETAIL OF THE STEEL FRAME BEING ATTACHED TO THE |
| EXISTING ELEVATOR SHAFT, BUT THERE IS NO INFORMATION AS |
| TO HOW THE MANUFACTURED BUILDING IS TRANSFERRING THE |
| LOADS TO THE STRUCTURAL STEEL FRAMEWORK, PART OF THE |
| MAIN WIND FORCE RESISTING SYSTEM. 2010 1609.4.1. |
| |
| 4) 2ND REQUEST. SHEET C4 THE ELEVATIONS INDICATE WHAT |
| APPEARS TO BE TRIM ON THE CONCEALMENT SCREENS AND |
| ARCHITECTURAL DECOR TO MATCH THE BUILDING ON THE |
| MODULAR BUILDING, PLEASE PROVIDE COMPLIANCE WITH: |
| |
| 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV |
| CONSTRUCTION. |
| ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, |
| EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE |
| CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5, |
| OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING |
| WITH THE FOLLOWING LIMITATIONS: |
| (2.) COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO |
| 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |