| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| SHEET A-2: THE EXISTING HVAC ROOM IS INDICATED AS BEING |
| A STORAGE ROOM. PER NFPA 1 SECTION 10.19.5.1, |
| COMBUSTIBLE MATERIAL SHALL NOT BE STORED IN MECHANICAL |
| ROOMS OR ELECTRICAL ROOMS. |
| |
| AS A NON-SEPARTED MIXED USE BUILDING, THE MOST STRIGENT |
| LIFE SAFETY ITEMS PER OCCUPANCY WILL BE APPLICABLE. |
| THEREFORE, PER NFPA 101 SECTION 38.3.4.1 A FIRE ALARM |
| SYSTEM SHALL BE PROVIDED WHERE THE BUILDING IS THREE OR |
| MORE STORIES IN HEIGHT. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| SYSTEM AND FIRE ALARM SYSTEM. |
| |
| SPRINKLER DRAWINGS: DRAWINGS REQUIRE ENGINEER'S |
| SIGN/SEAL. FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY |
| AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA |
| 72. |
| |
| SPRINKLER DRAWINGS: INDICATE THE SYSTEM IMPROVEMENTS |
| THAT WILL BE IMPLEMENTED TO BRING THE EXISTING PIPE |
| SCHEDULE INTO COMPLIANCE WITH NFPA 13. NOTE: PER NFPA |
| 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE BEEN IN |
| SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR |
| REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS |
| SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT |
| 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION, |
| SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED |
| TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING |
| JURISDICTION FOR FIELD SERVICE TESTING. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |