2013-07-26 10:46:192119 SOUTH DIXIE HIGHWAY
 PERMIT #13010089
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-2: THE EXISTING HVAC ROOM IS INDICATED AS BEING
 A STORAGE ROOM. PER NFPA 1 SECTION 10.19.5.1,
 COMBUSTIBLE MATERIAL SHALL NOT BE STORED IN MECHANICAL
 ROOMS OR ELECTRICAL ROOMS.
  
 AS A NON-SEPARTED MIXED USE BUILDING, THE MOST STRIGENT
 LIFE SAFETY ITEMS PER OCCUPANCY WILL BE APPLICABLE.
 THEREFORE, PER NFPA 101 SECTION 38.3.4.1 A FIRE ALARM
 SYSTEM SHALL BE PROVIDED WHERE THE BUILDING IS THREE OR
 MORE STORIES IN HEIGHT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 SPRINKLER DRAWINGS: DRAWINGS REQUIRE ENGINEER'S
 SIGN/SEAL. FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY
 AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA
 72.
  
 SPRINKLER DRAWINGS: INDICATE THE SYSTEM IMPROVEMENTS
 THAT WILL BE IMPLEMENTED TO BRING THE EXISTING PIPE
 SCHEDULE INTO COMPLIANCE WITH NFPA 13. NOTE: PER NFPA
 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE BEEN IN
 SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR
 REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS
 SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT
 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION,
 SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED
 TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION FOR FIELD SERVICE TESTING.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730