Plan Review Notes
Plan Review Notes For Permit 13010089
Permit Number 13010089
Review Stop E
Sequence Number 1
Notes
Date Text
2013-01-09 09:18:5213010089
 2119 S. DIXIE HIGHWAY
 INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE
 EQUIPMENT AND PANEL BOARDS. VERIFY THE EQUIPMENT FAULT
 CURRENT RATING IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE
 FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION, HIGH-LEG MARKING, AND THE ELECTRICAL
 SERVICE EQUIPMENT AND DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE PANEL BOARD SCHEDULES SHOWING BALANCED LOADS.
 INCLUDE A SUMMARY LOAD CALCULATION FOR THE SERVICE
 EQUIPMENT. NEC 210.3, 215.2, 220.40, 408.4
  
 VERIFY SAFETY CLEARANCES HAVE BEEN OBSERVED FOR PANEL
 ?C?. NEC 215.5, 110.26
  
 PROVIDE DEDICATED 20 AMPERE BRANCH CIRCUIT (S) FOR
 SIGNAGE. NEC 600.5
  
 RECEPTACLE OUTLETS ARE REQUIRED FOR SHOW WINDOWS. NEC
 210.62, 220.14, 220.40, 220.43
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  