2013-01-09 09:18:52 | 13010089 |
| 2119 S. DIXIE HIGHWAY |
| INTERIOR RENOVATION |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE |
| EQUIPMENT AND PANEL BOARDS. VERIFY THE EQUIPMENT FAULT |
| CURRENT RATING IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE |
| FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9 |
| |
| AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| SERVICE GROUND. NEC 250.94 |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH |
| PROTECTION, HIGH-LEG MARKING, AND THE ELECTRICAL |
| SERVICE EQUIPMENT AND DISCONNECTING MEANS. |
| NEC 110.22, 110.16, 110.22 |
| |
| PROVIDE PANEL BOARD SCHEDULES SHOWING BALANCED LOADS. |
| INCLUDE A SUMMARY LOAD CALCULATION FOR THE SERVICE |
| EQUIPMENT. NEC 210.3, 215.2, 220.40, 408.4 |
| |
| VERIFY SAFETY CLEARANCES HAVE BEEN OBSERVED FOR PANEL |
| ?C?. NEC 215.5, 110.26 |
| |
| PROVIDE DEDICATED 20 AMPERE BRANCH CIRCUIT (S) FOR |
| SIGNAGE. NEC 600.5 |
| |
| RECEPTACLE OUTLETS ARE REQUIRED FOR SHOW WINDOWS. NEC |
| 210.62, 220.14, 220.40, 220.43 |
| |
| GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS. |
| NEC 422.52 |
| |
| ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST |
| BE GFCI PROTECTED. NEC 210.8 |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE |
| WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC |
| ENERGY CONSERVATION 505.3 |
| |
| NOTE: |
| SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, |
| DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING. |
| |