2013-01-10 14:11:35BUILDING PLAN REVIEW
 PERMIT: 13010089
 ADD: 2119 S DIXIE HWY
 CONT: SOUTHEAST CONSTRUCTION.
 TEL: (954)394-3991
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 JAN. 11/2013
 1ST REVIEW
 ACTION: DENIED
  
 1) NOTE: SHEET SP-1 INDICATES THIS PROJECT CONSIST OF A
 LEVEL 2 ALTERATION. PLEASE UPDATE THE PERMIT
 APPLICATION AS WELL AS SP-1 TO INDICATE THIS PROJECT IS
 CONSIDERED A CHANGE OF OCCUPANCY SINCE IT IS A CHANGE
 OF USE FROM A AUTOMOBLIE DEALERSHIP MIXED USE SERVICE
 DEPARTMENT, STORAGEAND THE CAR SHOWROOM, SALES OFFICES
 BEING MERCANTILE. THE LAST RECORDED USE WAS RAGTOPS A
 AUTOMOBILE DEALERSHIP. A BUSINESS CAME IN AND RECEIVED
 A BUSINESS TAX LICENSE KIRKLAND EVENTS DESTINATION
 SERVICES BUT NEVER CAME IN FOR A CHANGE IN OCCUPANCY
 WHICH WOULD HAVE CREATED A MIXED USE BUILDING.
  
 2) SHEET SP-1 THE DESIGNER OF RECORD HAS NOT INDICATED
 IF THE PROPOSED DESIGN IS:
 2A) 2010 EXISTING BUILDING CODE 912.1.1.1 CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION.
 OR
 2B) 2010 EXISTING BUILDING CODE 912.1.1.2 CHANGE OF
 OCCUPANCY CLASSIFICATION WITH SEPARATION.
  
 3) SHEET SP-1 THE WIND DESIGN CRITERIA INDICATES THE
 DESIGN TO ASCE 7-10 THE CURRENT WIND DESIGN BUT THE
 WRONG WIND SPEED FOR A CATEGORY II BUILDING PLEASE SEE
 2010 FBC-B FIGURE 1609A VULT 170 MPH.
  
 4A) SHEET SP-1, OCCUPANT LOAD CHART, FIRST FLOOR THE
 RETAIL LOUNGE, RETAIL BOUTIQUE & COFFEE SHOP ALL LIST
 60 SQ FT PER OCCUPANT PLEASE REVIEW 2010 FBC-B TABLE
 1004.1.1 FOR MERCANTILE GRADE FLOOR AT 30 SQ FT/
 OCCUPANT.
  
 4B) SHEET SP-1 INDICATES A NEW DINING AREA BUT THE
 PLANS DO NOT INDICATE THE USE OF A KITCHEN AND DISH
 WASHING AREA, PLEASE BE AWARE OF 2010 EXST BLDG CODE
 SECTION
 910.3 INTERCEPTOR REQUIRED. IF THE NEW OCCUPANCY WILL
 PRODUCE GREASE OR OIL-LADEN WASTES, INTERCEPTORS SHALL
 BE PROVIDED AS REQUIRED IN THE FLORIDA BUILDING CODE,
 PLUMBING.
  
 5) SHEET SP-1 LIFE SAFETY PLAN, PLEASE PROVIDE THE
 FURNATURE LAYOUT FOR MEANS OF EGRESS, AACCESSIBLE PATH
 OF TRAVEL ... EXST BLDG CODE 905.1.
  
 6) SHEET SP-1 LIFE SAFETY PLAN, PLEASE PROVIDE THE
 INTENDED USE FOR THE LOBBY AREA THE OCCUPANT LOAD OF
 100 SQ FT PER OCCUPANT DOES NOT DECLARE TYPE OF USAGE
 PROVIDED SUCH AS MERCANTILE, STORAGE ... 2010 FBC-B.
 302.1 STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED BELOW. A ROOM OR SPACE THAT IS
 INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
 STRUCTURES WITH MULTIPLE OCCUPANCIES OR USES SHALL
 COMPLY WITH SECTION 508. WHERE A STRUCTURE IS PROPOSED
 FOR A PURPOSE THAT IS NOT SPECIFICALLY PROVIDED FOR IN
 THIS CODE, SUCH STRUCTURE SHALL BE CLASSIFIED IN THE
 GROUP THAT THE OCCUPANCY MOST NEARLY RESEMBLES,
 ACCORDING TO THE FIRE SAFETY AND RELATIVE HAZARD
 INVOLVED.
  
 7A) SHEET SP-1 FREIGHT ELEVATOR. 2010 EXISTING BUILDING
 CODE IN EITHER CASE IF THE DESIGNER OF RECORD CHOICES
 912.1.1.1 OR 912.1.1.2 SEPERATED OR NON-SEPERATED USE
 BOTH CODE SECTIONS REFER YOU BACK TO CHAPTER 8 FOR THE
 NEW OCCUPANCY CLASSIFICATION IN THE BUILDING AND THE
 REQUIREMENTS OF THIS CHAPTER. THE PROVISIONS
 ESSENTIALLY CLASSIFY CHANGES OF OCCUPANCY
 CLASSIFICATION AS LEVEL 3 ALTERATIONS. BY DIRECTLY
 STATING THE REQUIEMENTS OF CHAPTER 8 SHALL OVERRIDES
 THE REQUIREMENT FOR THE RECONFIGURATION OR ALTERATION
 TO BE OCCURRING IN THE 50 PER CENT OR MORE OF THE TOTAL
 BUILDING. THE APPLICATION OF CHAPTER 8 IN TURN REQUIRES
 COMPLIANCE WITH CHAPTERS 6 & 7 AS STATED IN SECTION
 801.2.
 2010 EXST BLDG CODE 703.2.1 EXISTING VERTICAL OPENINGS.
 ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO
 OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE
 SECTIONS OF THE FLORIDA FIRE PREVENTION CODE.
 2010 EXST BLDG CODE 912.7 ENCLOSURE OF VERTICAL SHAFTS.
 ENCLOSURE OF VERTICAL SHAFTS SHALL BE IN ACCORDANCE
 WITH SECTIONS 912.7.1 THROUGH 912.7.4.
 2010 EXST BLDG CODE 912.7.3 OTHER VERTICAL SHAFTS.
 INTERIOR VERTICAL SHAFTS OTHER THAN STAIRWAYS,
 INCLUDING BUT NOT LIMITED TO ELEVATOR HOISTWAYS AND
 SERVICE AND UTILITY SHAFTS, SHALL BE ENCLOSED AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING WHEN
 THERE IS A CHANGE OF USE TO A HIGHER HAZARD CATEGORY AS
 SPECIFIED IN TABLE 912.4.
  
 2010 EXST BLDG CODE 912.7.4 OPENINGS. ALL OPENINGS INTO
 EXISTING VERTICAL SHAFT ENCLOSURES SHALL BE PROTECTED
 BY FIRE ASSEMBLIES HAVING A FIRE-PROTECTION RATING OF
 NOT LESS THAN 1 HOUR AND SHALL BE MAINTAINED
 SELF-CLOSING OR SHALL BE AUTOMATIC CLOSING BY ACTUATION
 OF A SMOKE DETECTOR. ALL OTHER OPENINGS SHALL BE FIRE
 PROTECTED IN AN APPROVED MANNER. EXISTING FUSIBLE
 LINK-TYPE AUTOMATIC DOOR-CLOSING DEVICES SHALL BE
 PERMITTED IN ALL SHAFTS EXCEPT STAIRWAYS IF THE FUSIBLE
 LINK RATING DOES NOT EXCEED 135?F (57?C).
  
 7B) SHEET SP-1 OPEN STAIRWELLS. EXST BLDG CODE 703.2.3
 SUPPLEMENTAL STAIRWAY ENCLOSURE REQUIREMENTS. WHERE THE
 WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR
 AREA, STAIRWAYS THAT ARE PART OF THE MEANS OF EGRESS
 SERVING THE WORK AREA SHALL, AT A MINIMUM, BE ENCLOSED
 WITH SMOKE-TIGHT CONSTRUCTION ON THE HIGHEST WORK AREA
 FLOOR AND ALL FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
  
 2010 EXST BLDG CODE 912.7.2 STAIRWAYS. WHEN A CHANGE OF
 OCCUPANCY CLASSIFICIATION IS MADE TO A HIGHER HAZARD
 CATEGORY AS SHOWN IN TABLE 912.4, INTERIOR STAIRWAYS
 SHALL BE ENCLOSED AS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING.
 EXCEPTIONS:
 1. IN OTHER THAN GROUP I OCCUPANCIES, AN ENCLOSURE
 SHALL NOT BE REQUIRED FOR OPENINGS SERVING ONLY ONE
 ADJACENT FLOOR AND THAT ARE NOT CONNECTED WITH
 CORRIDORS OR STAIRWAYS SERVING OTHER FLOORS.
 2. UNENCLOSED EXISTING STAIRWAYS NEED NOT BE ENCLOSED
 IN A CONTINUOUS VERTICAL SHAFT IF EACH STORY IS
 SEPARATED FROM OTHER STORIES BY 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION OR APPROVED WIRED
 GLASS SET IN STEEL FRAMES AND ALL EXIT CORRIDORS ARE
 SPRINKLERED. AN OPENING BETWEEN THE CORRIDOR AND THE
 OCCUPANT SPACE SHALL HAVE AT LEAST ONE SPRINKLER HEAD
 ABOVE THE OPENINGS ON THE TENANT SIDE. THE SPRINKLER
 SYSTEM SHALL BE PERMITTED TO BE SUPPLIED FROM THE
 DOMESTIC WATER-SUPPLY SYSTEMS, PROVIDED THE SYSTEM IS
 OF ADEQUATE PRESSURE, CAPACITY, AND SIZING FOR THE
 COMBINED DOMESTIC AND SPRINKLER REQUIREMENTS.
  
  
 NOTE: 2010 EXST BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
  
 8) SECTION 904 FIRE PROTECTION 904.1 GENERAL. FIRE
 PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED, THE COVER SHEET INDICATES THIS TO BE A
 FULLY SPRINKLERED BUILDING.
  
 9) SECTION 905 MEANS OF EGRESS. 905.1 GENERAL.
 MEANS OF EGRESS IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 SECTION 912.
 EXST BLDG CODE912.4.1 MEANS OF EGRESS FOR CHANGE TO
 HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 10) 2010 EXST BLDG CODE SECTION 906 ACCESSIBILITY 906.1
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 2010 EXST BLDG CODE 912.8 ACCESSIBILITY. EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 2010 ACCESSIBILTY CODE (FL GRAY BOX) 201.1.1 VERTICAL
 ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 SEE EXCEPTIONS.
 BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN.
  
 2010 ACCESSIBILITY CODE.202.4 ALTERATIONS AFFECTING
 PRIMARY FUNCTION AREAS.
 IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION
 THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS
 TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE,
 THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE
 REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING
 THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE
 BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH
 ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL
 ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1.
 ALTERATIONS TO WINDOWS, HARDWARE, CONTROLS, ELECTRICAL
 OUTLETS, AND SIGNAGE SHALL NOT BE DEEMED TO BE
 ALTERATIONS THAT AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 NOTE THIS REVIEW IS STOPPED BECAUSE OF EXCESSIVE CODE
 VIOLATION!!!!! A THOROUGH REVIEW CAN NOT BE MADE AT
 THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION
 REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT
 PART OF THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  