Plan Review Notes
Plan Review Notes For Permit 11040253
Permit Number 11040253
Review Stop B
Sequence Number 3
Notes
Date Text
2011-07-08 14:17:25BUILDING PROVISO
  
 1) SUBMIT TWO SETS OF WALL DETAILS THAT SPECIFY THE
 FILE NUMBER OR DESIGN NUMBER OF THE ONE HOUR FIRE-RATED
 SEPARATION WALL BETWEEN THE TWO UNITS. ANSI/UL 263 IS
 THE TEST METHOD AND ACCEPTANCE CRITERIA.
  
 2) SUBMIT TWO SETS OF CORRECTED ENERGY CALCULATIONS.
 THE ONES THAT WERE SUBMITTED ARE INCORRECT. THE NUMBER
 OF WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE
 PLANS SHOW A GABLE ROOF NOT A HIP. THIS COMMENT WAS
 UNDER MECHANICAL REVIEW IN THE FIRST REVIEW. THE FORM
 DOES NOT SPECIFY TWO UNITS. THE COMMON WALL BETWEEN THE
 TWO UNITS IS NOT LISTED ON THE FORM. THERE ARE ONLY TWO
 DOORS AND THE FORM LISTS THREE. THE FORM ONLY LISTS 8
 WINDOWS AND THE ELEVATION PLANS SHOW 14.
  
 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS REQUIRED
 BY FBC R301.2.1.2 AND FBC EXISTING BUILDING 606.4.
 UNLESS THERE ARE EXISTING STORM PANELS, SUBMIT TWO
 COPIES OF PRODUCT APPROVALS AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]