2008-11-08 08:26:04 
  
 DENIED
  
 1) PER ENGINEERING WIND LOAD SHEETS AND SHUTTER
 SCHEDULE SEVERAL UNITS HAVE A SPAN LESS THAN 7'-9" THIS
 WOULD REQUIRE A DESIGN PRESSURE OF +57.2/-76.6 PSF AND
 IN TURN WOULD CHANGE THE O/C SPACING.
  
 2) THE SHUTTER SCHEDULE SHOWS ALL CONNECTIONS TO BE
 CEILING AND FLOOR MOUNTS, "G" TOP AND "I" BOTTOM BUT
 THE DRAWINGS ARE MARKED WITH A WALL MOUNT METHOD "B"
 TOP AND "E" BOTTOM PLEASE CLARIFY WHAT WILL BE USED.
  
 BLDG PLAN REVIEW