Date |
Text |
2007-01-22 13:13:20 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| |
| 1. SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY |
| ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF THE AREAS BEING |
| DRAINED. SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| PARAPETS ADDED TO THE SF OF THE ROOF. PLEASE SHOW THE |
| NEW AREA BEING ADDED TO THE ROOF WHERE THE LOWER ROOF |
| WILL BE COVERED BY THE NEW ROOF. INDICATE THE SIZE OF |
| THE EXISTING ROOF DRAINS AND THE PIPING SIZE OF THE |
| RWL'S AND BLDG. STORM DRAIN PIPING. SECTIONS 1106 & |
| 1107 WITH ALL SUBSECTIONS & TABLES. SECTION 106.1.1. |
| |
| 2. SHT A3 MORE INFORMATION IS REQUIRED. DETAILS 1 & 2 |
| INDICATE THAT THE ROOF ELEVATION IS 13'2", BUT DETAIL 2 |
| SHOWS ONE 6"X12" SCUPPER WHICH APPEARS TO BE BELOW THE |
| ROOF ELEVATION. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 3. SHT A3.1 DETAIL 1 INDICATE THE ELEVATION OF THE |
| EXISTING ROOF AND THE ELEVATION OF THE NEW ROOF. PLEASE |
| PROVIDE A DETAIL SHOWING HOW THE NEW ROOF CONNECTS TO |
| THE EXISTING ROOF WHICH IS INDICATED AS 13'2". |
| |
| 4. SUBMIT A DETAIL FOR THE EXISTING ROOF SHOWING ALL |
| EXISTING PRIMARY AND SECONDARY ROOF DRAINS. |
| |
| 5. SHT A3.1 DETAILS 4 & 5 LOWER ROOF IS NOT INDICATED |
| ON THE ELEVATION SECTIONS ON SHT A-3. PLEASE INDICATE |
| WHERE THESE LOWER ROOFS ARE ON THE ELEVATIONS TO |
| CLARIFY THE LOCATIONS. SECTION 106.1.1. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |