2007-01-22 13:13:20DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 1. SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF THE AREAS BEING
 DRAINED. SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO THE SF OF THE ROOF. PLEASE SHOW THE
 NEW AREA BEING ADDED TO THE ROOF WHERE THE LOWER ROOF
 WILL BE COVERED BY THE NEW ROOF. INDICATE THE SIZE OF
 THE EXISTING ROOF DRAINS AND THE PIPING SIZE OF THE
 RWL'S AND BLDG. STORM DRAIN PIPING. SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS & TABLES. SECTION 106.1.1.
  
 2. SHT A3 MORE INFORMATION IS REQUIRED. DETAILS 1 & 2
 INDICATE THAT THE ROOF ELEVATION IS 13'2", BUT DETAIL 2
 SHOWS ONE 6"X12" SCUPPER WHICH APPEARS TO BE BELOW THE
 ROOF ELEVATION. PLEASE CLARIFY. SECTION 106.1.1.
  
 3. SHT A3.1 DETAIL 1 INDICATE THE ELEVATION OF THE
 EXISTING ROOF AND THE ELEVATION OF THE NEW ROOF. PLEASE
 PROVIDE A DETAIL SHOWING HOW THE NEW ROOF CONNECTS TO
 THE EXISTING ROOF WHICH IS INDICATED AS 13'2".
  
 4. SUBMIT A DETAIL FOR THE EXISTING ROOF SHOWING ALL
 EXISTING PRIMARY AND SECONDARY ROOF DRAINS.
  
 5. SHT A3.1 DETAILS 4 & 5 LOWER ROOF IS NOT INDICATED
 ON THE ELEVATION SECTIONS ON SHT A-3. PLEASE INDICATE
 WHERE THESE LOWER ROOFS ARE ON THE ELEVATIONS TO
 CLARIFY THE LOCATIONS. SECTION 106.1.1.
  