2006-06-02 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 471.025 FS & 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE INITIALS ARE NOT
 ACCEPTABLE PER F.B.P.E.
  