Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) SMOKE DETECTORS IN HALLWAYS ARE TO | | BE INSTALLED AT LEAST THREE FEET FROM | | AIR CONDITIONER DIFFUSERS. | | 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | TO BE AUDIBLE THROUGHOUT BUILDING. | | 3) FIRE ALARM SYSTEM AND FIRE SPRINKLER | | SYSTEM TO BE MONITORED BY A LICENSED | | UL LISTED CENTRAL STATION. | | 4) ENTIRE SYSTEM TO BE TESTED WITH THE | | FIRE RESCUE DEPARTMENT. | | 5) SYSTEM TO BE INSTALLED IN ACCORDANCE | | WITH NFPA 72. | | 6) THE SINGLE STATION SMOKE DETECTORS | | INSTALLED WITHIN THE APARTMENTS ARE TO | | BE AUDIBLE WITHIN THE SLEEPING ROOMS OF | | THAT UNIT. | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|