Plan Review Details - Permit 20080134
Plan Review Stops For Permit 20080134
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By rmcphers Date 2020-09-15 Time 12:51 Rev Time 0.00
Received By rmcphers Date 2020-09-15 Time 12:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-31 Cont ID  
Sent By rmcphers Date 2020-08-31 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2020-08-31 Time 12:35 Sent To  
Notes
2020-08-31 12:40:31DOOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) COPY OF THE PRODUCT APPROVAL
 LISTED IN THE WIND LOAD ENGINEERING DOCUMENTS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-09-10 Cont ID  
Sent By pleduc Date 2020-09-10 Time   Rev Time 0.00
Received By pleduc Date 2020-09-10 Time 11:10 Sent To  
Notes
2020-09-10 11:14:01ENSURE FREE EGRESS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-09-02 Cont ID  
Sent By pleduc Date 2020-09-02 Time   Rev Time 0.00
Received By pleduc Date 2020-09-02 Time 13:28 Sent To  
Notes
2020-09-02 13:42:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS WTHIN THE BACK UP INFORMATION
 THAT THERE ARE TWO DOORS BEING REPLACED "3RD FLOOR AND
 2ND FLOOR LEFT HAND OUTSWING".
  
 THE APPLICATION STATES "REPLACE 1 HOLLOW METAL DOOR IN
 STAIRWELL"
  
 PLEASE REVIEW AND PROVIDE A DETILED SCOPE OF WORK AND
 AN APPLICABLE FLOOR PLAN SHOWING THE EXACT LOCATION OF
 THE DOOR(S).
  
  
  
 2) THERE IS AN INDICATION WITHIN THE BACKUP INFORMATION
 OF "RE-USING ELECTRIC STRIKE" .
  
 THERE IS NO ELECTRICAL PERMIT AND ANY WORK INVLOVING
 ACCESS CONTROL SHALL BE DONE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE CLOUDED NOTE.
  
  
 2A) IF THE ELECTRIC STRIKE IS TIED INO THE FIRE ALARM,
 THE FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWING BY A CERTIFIED FACONTRACTOR.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE CLOUDED NOTE.
  
  
  
 3) MOST STAIRWELL DOORS ARE INSTALL WITH A FIRE RATING.
 THE LOCATIONS OF THESE DOORS CAN NOT BE DETERMINED WITH
 WHAT IS PROVIDED TO CONFIRM INTENDED FIRE RATING ON
 ORIGINAL BUILDING PERMITS.
  
 THERE IS NO INDICATION THAT THESE NEW DOORS HAVE THE
 REQUIRED FIRE RATING.
  
 PLEASE REVIEW AND PROVIDE FOR ANY EXISTING FIRE DOOR
 RATING WITH THE REQUIRED RATING FOR THE NEW DOORS OR
 JUSTIFY WITH SPECIFIC DETAILS OF NONRATED DOORS AND
 NARRTIVE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-15 Cont ID  
Sent By rmcphers Date 2020-09-15 Time 12:51 Rev Time 0.00
Received By rmcphers Date 2020-09-09 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-09 Cont ID  
Sent By lmarchan Date 2020-09-03 Time 14:10 Rev Time 0.00
Received By lmarchan Date 2020-08-04 Time 16:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By rmcphers Date 2020-09-15 Time 12:51 Rev Time 0.00
Received By rmcphers Date 2020-09-15 Time 12:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-31 Cont ID  
Sent By rmcphers Date 2020-08-31 Time 12:41 Rev Time 0.00
Received By rmcphers Date 2020-08-31 Time 12:41 Sent To  
Notes
***NONE***