2020-09-02 13:42:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE ARE INDICATIONS WTHIN THE BACK UP INFORMATION |
| THAT THERE ARE TWO DOORS BEING REPLACED "3RD FLOOR AND |
| 2ND FLOOR LEFT HAND OUTSWING". |
| |
| THE APPLICATION STATES "REPLACE 1 HOLLOW METAL DOOR IN |
| STAIRWELL" |
| |
| PLEASE REVIEW AND PROVIDE A DETILED SCOPE OF WORK AND |
| AN APPLICABLE FLOOR PLAN SHOWING THE EXACT LOCATION OF |
| THE DOOR(S). |
| |
| |
| |
| 2) THERE IS AN INDICATION WITHIN THE BACKUP INFORMATION |
| OF "RE-USING ELECTRIC STRIKE" . |
| |
| THERE IS NO ELECTRICAL PERMIT AND ANY WORK INVLOVING |
| ACCESS CONTROL SHALL BE DONE UNDER SEPARATE PERMIT AND |
| SHOP DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE CLOUDED NOTE. |
| |
| |
| 2A) IF THE ELECTRIC STRIKE IS TIED INO THE FIRE ALARM, |
| THE FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| AND SHOP DRAWING BY A CERTIFIED FACONTRACTOR. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE CLOUDED NOTE. |
| |
| |
| |
| 3) MOST STAIRWELL DOORS ARE INSTALL WITH A FIRE RATING. |
| THE LOCATIONS OF THESE DOORS CAN NOT BE DETERMINED WITH |
| WHAT IS PROVIDED TO CONFIRM INTENDED FIRE RATING ON |
| ORIGINAL BUILDING PERMITS. |
| |
| THERE IS NO INDICATION THAT THESE NEW DOORS HAVE THE |
| REQUIRED FIRE RATING. |
| |
| PLEASE REVIEW AND PROVIDE FOR ANY EXISTING FIRE DOOR |
| RATING WITH THE REQUIRED RATING FOR THE NEW DOORS OR |
| JUSTIFY WITH SPECIFIC DETAILS OF NONRATED DOORS AND |
| NARRTIVE. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |