Plan Review Details - Permit 19061346
Plan Review Stops For Permit 19061346
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-12 Cont ID  
Sent By pvalenti Date 2019-07-12 Time 14:06 Rev Time 0.00
Received By pvalenti Date 2019-07-12 Time 14:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By shill Date 2019-07-05 Time 14:01 Rev Time 0.00
Received By shill Date 2019-07-05 Time 14:01 Sent To  
Notes
2019-07-05 14:06:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PROVIDE A PLAN SHOWING LOCATION OF PROPOSED
 DOORS.
  
 2. FBC B 1010.1.10, LABEL ROOMS SERVED WITH OCCUPANCY
 CLASSIFICATION OR ROOM DESIGNATION. NOTE THAT PANIC
 BARS/FIRE EXIT HARDWARE (AND OUTSWING) IS REQUIRED FOR
 ASSEMBLY OCCUPANCY AND ELECTRICAL ROOMS WITH EQUIPMENT
 RATED 1200 AMPERES OR MORE AND OVER 6' WIDE, AND THAT
 CONTAIN OVERCURRENT DEVICES, SWITCHING DEVICES OR
 CONTROL DEVICES.
  
 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-05 Cont ID  
Sent By shill Date 2019-07-05 Time 14:06 Rev Time 0.00
Received By shill Date 2019-06-27 Time 11:10 Sent To  
Notes
***NONE***