Plan Review Details - Permit 17071242
Plan Review Stops For Permit 17071242
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-31 Cont ID  
Sent By lcrespo Date 2017-08-31 Time 16:35 Rev Time 0.00
Received By lcrespo Date 2017-08-31 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-03 Cont ID  
Sent By gjohnson Date 2017-08-03 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2017-08-03 Time 16:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-31 Cont ID  
Sent By lcrespo Date 2017-08-31 Time 16:36 Rev Time 0.00
Received By lcrespo Date 2017-08-31 Time 16:35 Sent To  
Notes
2017-08-31 16:37:47APPROVED 8/31/17
  
 SENT TO UTILITIES FOR REVIEW

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-03 Cont ID  
Sent By gjohnson Date 2017-08-03 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2017-08-03 Time 16:01 Sent To  
Notes
2017-08-03 16:02:061) PLEASE INDICATE THE MODEL OF THE PVB ON THE
 SPECIFICATIONS ONE IS NOT LEAD FREE AS REQUIRED BY THE
 CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL
 AND ONLY THE NON-LEAD FREE DEVICE IS NOTED ON THE
 SPECIFICATION SHEET AS BEING ON THE USC LIST OF
 APPROVED DEVICES.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
 3) THE LEAD FREE MODEL OF THE PVB IS NOT LISTED ALL
 BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES.
 4) PLEASE INDICATE ON APPLICATION WHERE THESE DEVISES
 WILL BE INSTALLED. PER WPB AMEND TO FBC 107.2.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  