Plan Review Details - Permit 17070423
Plan Review Stops For Permit 17070423
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-18 Cont ID  
Sent By jleahy Date 2017-09-18 Time 09:11 Rev Time 0.00
Received By jleahy Date 2017-09-18 Time 09:11 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jleahy Date 2017-07-28 Time 11:35 Rev Time 0.00
Received By jleahy Date 2017-07-28 Time 11:35 Sent To  
Notes
2017-07-28 11:38:24FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW WHERE ELECTRIC COMES FROM AND WHAT SIZE
 BRANCH CIRCUITS ARE GOING TO BE USED.
  
 EF CONTRACTOR NOT ALLOWED BY CERTIFICATION TO DO THE
 HIGH VOLTAGE WORK. (OVER 99 VOLTS)
  
 NEED A SEPARATE PERMIT FOR THE ELECTRIC.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-27 Cont ID  
Sent By scaldero Date 2017-07-27 Time 08:09 Rev Time 0.00
Received By scaldero Date 2017-07-27 Time 08:06 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-28 Cont ID  
Sent By jleahy Date 2017-07-28 Time 11:38 Rev Time 0.00
Received By jleahy Date 2017-07-21 Time 09:55 Sent To  
Notes
2017-07-28 11:42:39VALUE CHARGED FOR THE WORK IS NOT ALL OF THE VALUE
 SHOWN ON PERMITS
  
 THE TOTAL SHOWN SHOULD BE $85,950 FOR ALL WORK MINUS
 HIGH VOLTAGE ELECTRICAL WORK.
  
 THERE ARE TWO APPLICATION IN THE PACKAGE FOR TWO PARTS
 OF THIS PROJECT.
  
 7/28/17 JLEAHY
2017-07-24 09:56:06ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-07-25 Cont ID  
Sent By llouie Date 2017-07-25 Time   Rev Time 0.00
Received By llouie Date 2017-07-25 Time 11:29 Sent To FIRE
Notes
2017-07-17 14:13:43ROUTED TO LINDA LOUIE