Plan Review Details - Permit 16111241
Plan Review Stops For Permit 16111241
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-09 Cont ID  
Sent By tklarge Date 2017-01-09 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2017-01-09 Time 07:31 Sent To  
Notes
2017-01-09 08:41:08 
 BUILDING PROVISO: ROOFTOP EQUIPMENT ON STANDS TO COMPLY
 WITH:
 2014 FBC-B TABLE 1509.6.5. WHERE ROOFING MATERIALS
 EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT SUPORTS PROVIDING
 A
 MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE
 1509.6.5.
 THE SUPPORTS PROVIDING CLEARANCE ARE THE HORIZONTAL
 SUPPORTS,
 THE VERTICAL DIMENSION SHOULD BE TAKEN FROM THE BOTTOM
 OF THE
 HORIZONTAL SUPPORTS TO THE FINISH ROOF DECK. IF THE
 HEATER IS
 BETWEEN 36-48 INCHES THEN THE CLEAR HEIGHT MINIMUM
 SHALL BE
 24 INCHES HIGH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-12 Cont ID  
Sent By   Date 2016-12-12 Time   Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time 06:03 Sent To  
Notes
2016-12-12 06:44:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16111241
 ADD: 5454 N. HAVERHILL RD. ASTROS HYDRO THERAPY SPAS
 CONT: SAMMET POOLS
 TEL: 954-530-1915
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 12/ 2016
 ACTION: DENIED
  
 1) SHEET 101716 ASTROS_SPAS-CS2.0 UNDER THE HEADING OF
 NOTES: IS GOING TO THE DEPARTMENT OF HEALTH FOR (2)
 VARIANCES 64E-9.006?2 MULTIPLE FLOOR LEVELS IN POOLS
 ARE PROHIBITED & 64E-9006?2 UNDERWATER SEATS BENCHES
 MAY BE INSTALLED IN AREAS LESS THAN 5 FEET DEEP.
 PLEASE SUBMIT APPROVAL AND RELIEF FROM THESE CODE
 ARTICLES.
  
 2) SHEET SPAS-CS1.0 IN THE UPPER RIGHT HAND CORNER OF
 THE SHEET LIST A NOTE SEE HEATER STAND DETAIL ON CS5.1.
 SHEET CS%
 ROOF TOP STAND INDICATES THE HEATER TO BE 40 WIDE AND
 THE CLEAR VERTICAL HEIGHT TO THE TOP OF THE STAND IS
 1FOOT 4 INCHES. PLEASE REVIEW SECTION 1509.6.5 AND
 TABLE 1509.6.5. OF THE 2014 FBC-B. WHERE ROOFING
 MATERIALS EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPORTS PROVIDING A MINIMUM CLEARANCE HEIGHT IN
 ACCORDANCE WITH TABLE 1509.6.5.
 THE SUPPORTS PROVIDING CLEARANCE ARE THE HORIZONTAL
 SUPPORTS, THE VERTICAL DIMENSION SHOULD BE TAKEN FROM
 THE BOTTOM OF THE HORIZONTAL SUPPORTS TO THE FINISH
 ROOF DECK. IF THE HEATER IS BETWEEN 36-48 INCHES THEN
 THE CLEAR HEIGHT MINIMUM SHALL BE 24 INCHES HIGH.
  
 3) PLEASE PROVIDE THE MANUFACTURES SPECIFICATION FOR
 THE SPA HEATERS. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED, TO DETERMINE CODE COMPLIANCE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-12-08 Cont ID  
Sent By vperez Date 2016-12-08 Time 13:45 Rev Time 0.00
Received By vperez Date 2016-12-08 Time 13:45 Sent To  
Notes
2016-12-08 13:46:25PERMIT FOR SPA HOOKUP PER PERMIT
  
 VAL PEREZ
 *6717

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2017-01-07 Cont ID  
Sent By tklarge Date 2017-01-07 Time 09:06 Rev Time 0.00
Received By tklarge Date 2017-01-07 Time 09:02 Sent To  
Notes
2017-01-07 09:08:18PLAN REVIEW FOR GAS PERMIT FOR THE INSTALLATION OF THE
 GAS POOL HEATER AND ASSOCIATED PIPING IS UNDER
 #16111245.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-12-10 Cont ID  
Sent By tklarge Date 2016-12-10 Time 08:59 Rev Time 0.00
Received By tklarge Date 2016-12-10 Time 08:59 Sent To  
Notes
2016-12-10 09:00:12A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS THAT
 REFLECT THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB
 AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-09 Cont ID  
Sent By jwitmer Date 2017-01-09 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2017-01-05 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-29 Cont ID  
Sent By lmarchan Date 2016-12-29 Time 11:56 Rev Time 0.00
Received By lmarchan Date 2016-11-30 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-07 Cont ID  
Sent By tklarge Date 2017-01-07 Time 09:02 Rev Time 0.00
Received By tklarge Date 2017-01-07 Time 08:04 Sent To  
Notes
2017-01-08 05:17:05PLUMBING PROVISO:
 THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY SECS.
 C404.7.2 ( TIME SWITH REQUIRED) & C404.7.3.( SPA COVER
 REQUIRED).

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-10 Cont ID  
Sent By tklarge Date 2016-12-10 Time 08:59 Rev Time 0.00
Received By tklarge Date 2016-12-10 Time 04:52 Sent To  
Notes
2016-12-10 07:42:311) SHT. CS.2.0 REFERS TO A REQUIRED VARIANCE FROM THE
 DEPT. OF HEALTH. IF THESE VARIANCES HAVE BEEN GRANTED,
 SUBMIT COPIES FOR REVIEW. ALSO, IF APPLICATION HAS BEEN
 MADE TO THE DEPT.OF HEALTH FOR AN OPERATING PERMIT,
 SUBMIT A COPY OF VERIFICATION THAT THE APPLICATION HAS
 BEEN RECEIVED FROM PBC DOH. 2014 FBC SEC. 454.1.1, WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER, THE NAIN DRAINS AND THE PUMPS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) THE CHLORINE ROOM SHALL COMPLY WITH 2014 FBC
 SEC.454.1.6.5.16.1.1.1.
 4) SHT. CS 5.1 - THE NON-ELECTRICAL EQUIPMENT TABLE
 CALLS OUT THE HOT SPA COLLECTOR TANK AS 690 GALLONS AND
 THE COLD SPA COLLECTOR TANK AS 460 GALLONS AND THE
 SCHEMATIC SHOWS 670 GALLONS FOR THE HOT AND 750 GALLONS
 FOR THE COLD. CLARIFY.
 5) SHT. CS 5.2 - HAS A REFERENCE TO DETAIL "A" ON
 SHT.CP5.0. THERE IS NO SUCH SHEET IN THIS SUBMITTAL.
 CLARIFY.
 6) THE GAS FOR THE SPA HEATERS SHALL BE A SEPARATE
 PERMIT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-01-09 Cont ID  
Sent By jwitmer Date 2017-01-09 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time   Sent To  
Notes
2017-01-07 09:09:14PLUMBING RELATED SHEETS VERIFIED. 1/7/17.TKL
2016-12-12 06:51:5112/12/2016 ALL SHEETS SIGNATURES VERIFIED. JW

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-19 Cont ID  
Sent By ajones Date 2016-12-19 Time 16:59 Rev Time 0.00
Received By ajones Date 2016-12-19 Time 16:59 Sent To  
Notes
***NONE***