2013-09-30 16:07:22 | BUILDING PLAN REVIEW |
| PERMIT: 13070610 |
| ADD: 720 S SAPODILLA AV- ROOFTOP |
| CONT: HAYDEN PROFESSIONAL SERVICES |
| TEL: (772)781-1512 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE:9/ 30/2012 |
| ACTION: DENIED |
| |
| 1) COMPLIED. PLANS BEING SUBMITTED FOR CITY REVIEW |
| REQUIRES CITY PLACE STAMP OF REVIEW AND APPROVAL. |
| |
| 2A) 3RD REVIEW. SUBMITTED IS A PRE-MANUFACTURED |
| BUILDING, THIS STATE APPROVED PLAN, HAS VARIOUS OPTIONS |
| AS TO VARIOUS OPTIONS TO 1 OR 2 HOUR FIRE RATINGS, |
| PLEASE CIRCLE WHICH OPTION WILL BE EXERCISED IN |
| BUILDING THIS UNIT. |
| THE ISSUE IS THIS MODULAR BUILDING IS GOING TO BE |
| LOCATED ON TOP OF AN EXISTING 5 STORY III-A FULLY |
| SPRINKLERED BUILDING. THE STATE APPROVED PLAN INDICATES |
| THIS TO BE A BUILDING TYPE V-B BUT WITH THE VARIOUS |
| OPTIONS IT CAN BE UPGRADED TO THE REQUIREMENTS OF A |
| BUILDING TYPE IIIA. |
| THE ORIGINAL BUILDING BEING BUILT AS A MIXED USE |
| MERCANTILE 1ST FLOOR AND R2 THE SECOND THRU 5TH FLOOR |
| WHICH ALLOWED FOR 4 STORIES, IT IS FULLY SPRINKLERED |
| WITH A FULL NFPA 13 SPRINKLER THAT GACE THEM A ONE |
| STORY INCREASE, THE NEW MODULAR STRUCTURE WOULD ALSO BE |
| REQUIRED TO BE FULLY SPRINKLERED AND A MINIMUM BUILDING |
| TYPE OF IIIA. |
| |
| 2B) WE WILL STILL NEED DOCUMENTATION THAT THIS BUILDING |
| WILL BE EITHER FIRE SPRINKLERED OR MEET THE REQUIREMENT |
| THROUGH AN ALTERNATE METHOD. |
| |
| 3) COMPLIED. 2ND REQUEST.SHEET S2 DETAIL # 5 INDICATES |
| A SPECIAL PLATE DETAIL OF THE STEEL FRAME BEING |
| ATTACHED TO THE EXISTING ELEVATOR SHAFT, BUT THERE IS |
| NO INFORMATION AS TO HOW THE MANUFACTURED BUILDING IS |
| TRANSFERRING THE LOADS TO THE STRUCTURAL STEEL |
| FRAMEWORK, PART OF THE MAIN WIND FORCE RESISTING |
| SYSTEM. 2010 1609.4.1. |
| |
| 4) 3RD REQUEST. SHEET C4 THE ELEVATIONS INDICATE WHAT |
| APPEARS TO BE TRIM ON THE CONCEALMENT SCREENS AND |
| ARCHITECTURAL DECOR TO MATCH THE BUILDING ON THE |
| MODULAR BUILDING, PLEASE PROVIDE COMPLIANCE WITH: |
| |
| 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV |
| CONSTRUCTION. |
| ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, |
| EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE |
| CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5, |
| OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING |
| WITH THE FOLLOWING LIMITATIONS: (2.) COMBUSTIBLE |
| ARCHITECTURAL TRIM SHALL BE LIMITED TO 40 FEET (12 192 |
| MM) IN HEIGHT ABOVE GRADE. |
| |
| SUBMITTED REPORTS:STEALTHSKIN V (FR-ESSV) CONSEALMENT |
| PANEL- OK MEETS THE REQUIREMENT |
| GLASTEEL FIRE RETARDANT LINER PANEL -OK MEETS THE |
| REQUIREMENT |
| 3" HARDCOAT FOAM, 60 MIL THICKNESS FAILS TO MEET THE |
| REQUIREMENT OF E84 COMPOSITE MATERIALS FLAME SPREAD NOT |
| GREATER THAN 50, TESTED THE FLAME SPREAD |
| WAS 140. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |