Plan Review Details - Permit 13070610
Plan Review Stops For Permit 13070610
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-01-31 Cont ID  
Sent By jwitmer Date 2014-01-31 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2014-01-31 Time 08:00 Sent To  
Notes
2014-01-31 08:36:05SUBMITTAL FOR NON-CONBUSTIBLE TRIM FOR THE TOP OF
 ANTENNA SCREEN & TELECOMUNICATION SHELTER. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-10-17 Cont ID  
Sent By jwitmer Date 2013-10-17 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2013-10-17 Time 08:27 Sent To  
Notes
2013-10-17 09:54:52BUILDING PLAN REVIEW
 PERMIT: 13070610
 ADD: 720 S SAPODILLA AV- ROOFTOP
 CONT: HAYDEN PROFESSIONAL SERVICES
 TEL: (772)781-1512
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: 10/17/2013
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) SHEET C4 THE ELEVATIONS INDICATE WHAT APPEARS TO BE
 TRIM ON THE CONCEALMENT SCREENS (CONCEALMENT SCREENS-
 CODE COMPLIANT/ MEETS NON-COMBUSTIBILITY REQUIREMENT)
 AND ARCHITECTURAL DECOR (ARCHITECTURAL DECOR/ 3"
 HARDCOATED FOAM MOLDINGS/ COMBUSTIBLE, NOT COMPLIANT
 FLAME SPREAD GREATER THAN 50 DOES NOT MEET ASTM E84 OR
 UL723) TO MATCH THE BUILDING ON THE MODULAR BUILDING,
 PLEASE PROVIDE COMPLIANCE WITH:
  
 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV
 CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5,
 OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING
 WITH THE FOLLOWING LIMITATIONS:
 (2.) COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-09-30 Cont ID  
Sent By jwitmer Date 2013-09-30 Time 15:34 Rev Time 0.00
Received By jwitmer Date 2013-09-30 Time 15:34 Sent To  
Notes
2013-09-30 16:07:22BUILDING PLAN REVIEW
 PERMIT: 13070610
 ADD: 720 S SAPODILLA AV- ROOFTOP
 CONT: HAYDEN PROFESSIONAL SERVICES
 TEL: (772)781-1512
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:9/ 30/2012
 ACTION: DENIED
  
 1) COMPLIED. PLANS BEING SUBMITTED FOR CITY REVIEW
 REQUIRES CITY PLACE STAMP OF REVIEW AND APPROVAL.
  
 2A) 3RD REVIEW. SUBMITTED IS A PRE-MANUFACTURED
 BUILDING, THIS STATE APPROVED PLAN, HAS VARIOUS OPTIONS
 AS TO VARIOUS OPTIONS TO 1 OR 2 HOUR FIRE RATINGS,
 PLEASE CIRCLE WHICH OPTION WILL BE EXERCISED IN
 BUILDING THIS UNIT.
 THE ISSUE IS THIS MODULAR BUILDING IS GOING TO BE
 LOCATED ON TOP OF AN EXISTING 5 STORY III-A FULLY
 SPRINKLERED BUILDING. THE STATE APPROVED PLAN INDICATES
 THIS TO BE A BUILDING TYPE V-B BUT WITH THE VARIOUS
 OPTIONS IT CAN BE UPGRADED TO THE REQUIREMENTS OF A
 BUILDING TYPE IIIA.
 THE ORIGINAL BUILDING BEING BUILT AS A MIXED USE
 MERCANTILE 1ST FLOOR AND R2 THE SECOND THRU 5TH FLOOR
 WHICH ALLOWED FOR 4 STORIES, IT IS FULLY SPRINKLERED
 WITH A FULL NFPA 13 SPRINKLER THAT GACE THEM A ONE
 STORY INCREASE, THE NEW MODULAR STRUCTURE WOULD ALSO BE
 REQUIRED TO BE FULLY SPRINKLERED AND A MINIMUM BUILDING
 TYPE OF IIIA.
  
 2B) WE WILL STILL NEED DOCUMENTATION THAT THIS BUILDING
 WILL BE EITHER FIRE SPRINKLERED OR MEET THE REQUIREMENT
 THROUGH AN ALTERNATE METHOD.
  
 3) COMPLIED. 2ND REQUEST.SHEET S2 DETAIL # 5 INDICATES
 A SPECIAL PLATE DETAIL OF THE STEEL FRAME BEING
 ATTACHED TO THE EXISTING ELEVATOR SHAFT, BUT THERE IS
 NO INFORMATION AS TO HOW THE MANUFACTURED BUILDING IS
 TRANSFERRING THE LOADS TO THE STRUCTURAL STEEL
 FRAMEWORK, PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM. 2010 1609.4.1.
  
 4) 3RD REQUEST. SHEET C4 THE ELEVATIONS INDICATE WHAT
 APPEARS TO BE TRIM ON THE CONCEALMENT SCREENS AND
 ARCHITECTURAL DECOR TO MATCH THE BUILDING ON THE
 MODULAR BUILDING, PLEASE PROVIDE COMPLIANCE WITH:
  
 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV
 CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5,
 OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING
 WITH THE FOLLOWING LIMITATIONS: (2.) COMBUSTIBLE
 ARCHITECTURAL TRIM SHALL BE LIMITED TO 40 FEET (12 192
 MM) IN HEIGHT ABOVE GRADE.
  
 SUBMITTED REPORTS:STEALTHSKIN V (FR-ESSV) CONSEALMENT
 PANEL- OK MEETS THE REQUIREMENT
 GLASTEEL FIRE RETARDANT LINER PANEL -OK MEETS THE
 REQUIREMENT
 3" HARDCOAT FOAM, 60 MIL THICKNESS FAILS TO MEET THE
 REQUIREMENT OF E84 COMPOSITE MATERIALS FLAME SPREAD NOT
 GREATER THAN 50, TESTED THE FLAME SPREAD
 WAS 140.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-21 Cont ID  
Sent By jwitmer Date 2013-08-21 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2013-08-21 Time 10:00 Sent To  
Notes
2013-08-21 11:59:27BUILDING PLAN REVIEW
 PERMIT: 13070610
 ADD: 720 S SAPODILLA AV- ROOFTOP
 CONT: HAYDEN PROFESSIONAL SERVICES
 TEL: (772)781-1512
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 8/ 21/2012
 ACTION: DENIED
  
 1) COMPLIED. PLANS BEING SUBMITTED FOR CITY REVIEW
 REQUIRES CITY PLACE STAMP OF REVIEW AND APPROVAL.
  
 2) 2ND REVIEW. SUBMITTED IS A PRE-MANUFACTURED
 BUILDING, IT APPEARS NOT TO BE A STATE APPROVED PLAN,
 SINCE THERE IS ONLY AN APPROVAL FROM PFS AND ONLY ON A
 FEW SHEETS,NOR IS THE SIGNATURE OF THE PLANS EXAMINER
 LICENSE NUMBER FOUND ON THE DBPR WEBSITE. THE
 ENGINEERING PROVIDED BY JOHN IRVING P. E. DOES INDICATE
 THIS STRUCTURE TO BE ELEVATED SINCE THERE IS A HEIGHT
 ADJUSTMENT FACTOR OF 1.62. THE ISSUE IS THIS MODULAR
 BUILDING IS GOING TO BE LOCATED ON TOP OF AN EXISTING 5
 STORY III-A FULLY SPRINKLERED BUILDING. AS INDICATED
 PAGE 1 OF 15 BUILDING TYPE V-B AND BUILDING LIMITATIONS
 1.3.3 OCCUPANCY S-2 OR B OR U FROM THE 2010 FBC-TABLE
 503THIS STRUCTURE CAN NOT BE PLACED ANY HIGHER THAN 2
 STORIES.
 THE ORIGINAL BUILDING BEING BUILT AS A MIXED USE
 MERCANTILE 1ST FLOOR AND R2 THE SECOND THRU 5TH FLOOR
 WHICH ALLOWED FOR 4 STORIES, IT IS FULLY SPRINKLERED
 WITH A FULL NFPA 13 SPRINKLER THAT GACE THEM A ONE
 STORY INCREASE, THE NEW MODULAR STRUCTURE WOULD ALSO BE
 REQUIRED TO BE FULLY SPRINKLERED AND A MINIMUM BUILDING
 TYPE OF IIIA.
  
 3) 2ND REQUEST.SHEET S2 DETAIL # 5 INDICATES A SPECIAL
 PLATE DETAIL OF THE STEEL FRAME BEING ATTACHED TO THE
 EXISTING ELEVATOR SHAFT, BUT THERE IS NO INFORMATION AS
 TO HOW THE MANUFACTURED BUILDING IS TRANSFERRING THE
 LOADS TO THE STRUCTURAL STEEL FRAMEWORK, PART OF THE
 MAIN WIND FORCE RESISTING SYSTEM. 2010 1609.4.1.
  
 4) 2ND REQUEST. SHEET C4 THE ELEVATIONS INDICATE WHAT
 APPEARS TO BE TRIM ON THE CONCEALMENT SCREENS AND
 ARCHITECTURAL DECOR TO MATCH THE BUILDING ON THE
 MODULAR BUILDING, PLEASE PROVIDE COMPLIANCE WITH:
  
 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV
 CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5,
 OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING
 WITH THE FOLLOWING LIMITATIONS:
 (2.) COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-02 Cont ID  
Sent By jwitmer Date 2013-07-29 Time 09:47 Rev Time 0.00
Received By jwitmer Date 2013-07-29 Time 06:58 Sent To  
Notes
2013-07-31 09:15:33BUILDING PLAN REVIEW
 PERMIT: 13070610
 ADD: 720 S SAPODILLA AV- ROOFTOP
 CONT: HAYDEN PROFESSIONAL SERVICES
 TEL: (772)781-1512
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 7/31/2012
 ACTION: DENIED
  
 1) PLANS BEING SUBMITTED FOR CITY REVIEW REQUIRES CITY
 PLACE STAMP OF REVIEW AND APPROVAL.
  
 2) THE PLANS INDICATE THE INSTALATION OF A MODULAR
 BUILDING BUT NO PLANS WERE SUBMITTED. IF THIS IS A
 STATE APPROVED MODULAR BUILDING PLANS STILL NEED TO BE
 SUBMITTED WITH THE STATE APPROVAL. NOTE THERE ARE
 LIMITATIONS ON STATE APPROVED PLANS REVIEW THE DESIGN
 PERAMTERS TO SEE IF IT WAS APPROVED WITH THE ASSOCAITED
 PRESSURES BEING PLACED AT THIS ELEVATION. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET S2 DETAIL # 5 INDICATES A SPECIAL PLATE DETAIL
 OF THE STEEL FRAME BEING ATTACHED TO THE EXISTING
 ELEVATOR SHAFT, BUT THERE IS NO INFORMATION AS TO HOW
 THE MANUFACTURED BUILDING IS TRANSFERRING THE LOADS TO
 THE STRUCTURAL STEEL FRAMEWORK, PART OF THE MAIN WIND
 FORCE RESISTING SYSTEM. 2010 1609.4.1.
  
 4) SHEET C4 THE ELEVATIONS INDICATE WHAT APPEARS TO BE
 TRIM ON THE CONCEALMENT SCREENS AND ARCHITECTURAL DECOR
 TO MATCH THE BUILDING ON THE MODULAR BUILDING, PLEASE
 PROVIDE COMPLIANCE WITH:
  
 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV
 CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5,
 OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING
 WITH THE FOLLOWING LIMITATIONS:
 (2.) COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 11:09 Rev Time 0.00
Received By dharvey Date 2013-08-15 Time 10:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-10-17 Cont ID  
Sent By jwitmer Date 2013-10-17 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2013-10-04 Time 06:00 Sent To  
Notes
2013-10-05 06:01:10SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-09-30 Cont ID  
Sent By jwitmer Date 2013-09-30 Time 16:07 Rev Time 0.00
Received By jwitmer Date 2013-09-26 Time 15:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-21 Cont ID  
Sent By jwitmer Date 2013-08-21 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2013-08-19 Time 16:25 Sent To  
Notes
2013-08-19 16:25:34SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 11:10 Rev Time 0.00
Received By dharvey Date 2013-07-17 Time 14:35 Sent To  
Notes
2013-08-15 11:10:30PLACED IN DENIED UNDER "H" DH
2013-07-18 14:35:24B14
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-14 Cont ID  
Sent By aaponte Date 2013-08-14 Time 16:30 Rev Time 1.00
Received By eschneid Date 2013-08-14 Time 16:30 Sent To  
Notes
2013-08-14 16:32:15PASSED W/PROVISOS
  
 1) THE APPLICANT?S ROOFTOP INSTALLATION SHALL BE
 PAINTED TO MATHC THE EXISTING BUILDING D?COR.
  
 2) THE GENERATOR NOISE LEVEL SHALL NOT EXCEED 45 DB(A)
 AT THE PROPERTY LINE AND SHALL BE TESTED ONLY BETWEEN
 THE HOURS OF 9AM AND 4PM MONDAY THROUGH FRIDAY.
  
2013-07-22 11:00:007/22/13