Plan Review Details - Permit 13010089
Plan Review Stops For Permit 13010089
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-08-16 Cont ID  
Sent By jwitmer Date 2013-08-16 Time 08:18 Rev Time 0.00
Received By jwitmer Date 2013-08-16 Time 08:18 Sent To  
Notes
2013-08-07 16:14:29NEW SHEETS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-20 Cont ID  
Sent By jwitmer Date 2013-07-20 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2013-07-20 Time 12:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-05-21 Cont ID  
Sent By JWITMER Date 2013-05-21 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2013-05-21 Time 13:03 Sent To  
Notes
2013-07-10 13:54:24CHECK VALUE. $20,000 TO DO A CHANGE OF
 USE FROM CAR DEALER TO RESTAURANT????.
 ELECTRICAL CONTRACTOR SUBMITTED
 SUBPERMIT APPLICATION 13070339 WITH A
 VALUE OF $20,000 JUST TO DO THE SERVICE
 CHANGE.???? JG.
  
  
  
2013-05-21 15:26:47BUILDING PLAN REVIEW
 PERMIT: 13010089
 ADD: 2119 S DIXIE HWY
 CONT: SOUTHEAST CONSTRUCTION.
 TEL: (954)394-3991
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 MAY 31/2013
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SHEET SP-1 THE DESIGNER OF RECORD HAS ELECTED TO USE
 2010 EXISTING BUILDING CODE 912.1.1.2 CHANGE OF
 OCCUPANCY CLASSIFICATION WITH SEPARATION. THE FIRST
 FLOOR THERE IS NO SEPERATION BETWEEN THE A2 RESTARAUNT
 AND THE MERCANTILE OCCUPANCIES, THEN THE DESIGNER DOES
 PROVIDE SERERATION BETWEEN THE A2 ASSEMBLY AND BUSINESS
 OCCUPANCIES.
  
 3) COMPLIED.
  
 4A) 2ND REQUEST. SHEET SP-1, OCCUPANT LOAD CHART, FIRST
 FLOOR THE RETAIL LOUNGE, RETAIL BOUTIQUE & COFFEE SHOP
 ALL LIST 60 SQ FT PER OCCUPANT PLEASE REVIEW 2010 FBC-B
 TABLE 1004.1.1 FOR MERCANTILE GRADE FLOOR AT 30 SQ FT/
 OCCUPANT.
  
 4B) COMPLIED. KITCHEN WILL COME IN UNDER SEPERATE
 PERMIT.
  
 5) SHEET SP-1 LIFE SAFETY PLAN, PLEASE PROVIDE THE
 FURNATURE LAYOUT FOR MEANS OF EGRESS, ACCESSIBLE PATH
 OF TRAVEL ... EXST BLDG CODE 905.1.
  
 6) COMPLIED.
  
 7A) 2ND REQUEST, SHEET SP-1 FREIGHT ELEVATOR. THE
 DESIGNER OF RECORD HAS NOT INDICATED THE EXISTING
 ELEVATOR WALLS ARE CREATING A RATED SHAFT, NOTED THE
 PLANS INDICATE THE USE OF FIRE SHUTTERS OVER THE
 OPENINGS. IN THE LAST MEETING THE FIRST FLOOR FIRE
 SHUTTER WAS GOING TO BE REMOVED IN CASE OF FIRE IF THIS
 ELEVATOR WAS GOING TO BE USED THEY COULD STILL GET OUT
 OF THE FREIGHT ELEVATOR.ITS THE SAME IDEA AS THE
 REQUIRED ELEVATOR LOBBY THAT WOULD STILL HAVE ONE MEANS
 OF EGRESS 708.14.1 WHEN THE FREIGHT ELEVATOR RETURNS TO
 THE FIRST FLOOR..
  
 2010 EXISTING BUILDING CODE IN EITHER CASE IF THE
 DESIGNER OF RECORD CHOICES 912.1.1.1 OR 912.1.1.2
 SEPERATED OR NON-SEPERATED USE BOTH CODE SECTIONS REFER
 YOU BACK TO CHAPTER 8 FOR THE NEW OCCUPANCY
 CLASSIFICATION IN THE BUILDING AND THE REQUIREMENTS OF
 THIS CHAPTER. THE PROVISIONS ESSENTIALLY CLASSIFY
 CHANGES OF OCCUPANCY CLASSIFICATION AS LEVEL 3
 ALTERATIONS. BY DIRECTLY STATING THE REQUIEMENTS OF
 CHAPTER 8 SHALL OVERRIDES THE REQUIREMENT FOR THE
 RECONFIGURATION OR ALTERATION TO BE OCCURRING IN THE 50
 PER CENT OR MORE OF THE TOTAL BUILDING. THE APPLICATION
 OF CHAPTER 8 IN TURN REQUIRES COMPLIANCE WITH CHAPTERS
 6 & 7 AS STATED IN SECTION 801.2.
 2010 EXST BLDG CODE 703.2.1 EXISTING VERTICAL OPENINGS.
 ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO
 OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE
 SECTIONS OF THE FLORIDA FIRE PREVENTION CODE.
 2010 EXST BLDG CODE 912.7 ENCLOSURE OF VERTICAL SHAFTS.
 ENCLOSURE OF VERTICAL SHAFTS SHALL BE IN ACCORDANCE
 WITH SECTIONS 912.7.1 THROUGH 912.7.4.
 2010 EXST BLDG CODE 912.7.3 OTHER VERTICAL SHAFTS.
 INTERIOR VERTICAL SHAFTS OTHER THAN STAIRWAYS,
 INCLUDING BUT NOT LIMITED TO ELEVATOR HOISTWAYS AND
 SERVICE AND UTILITY SHAFTS, SHALL BE ENCLOSED AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING WHEN
 THERE IS A CHANGE OF USE TO A HIGHER HAZARD CATEGORY AS
 SPECIFIED IN TABLE 912.4.
  
 2010 EXST BLDG CODE 912.7.4 OPENINGS. ALL OPENINGS INTO
 EXISTING VERTICAL SHAFT ENCLOSURES SHALL BE PROTECTED
 BY FIRE ASSEMBLIES HAVING A FIRE-PROTECTION RATING OF
 NOT LESS THAN 1 HOUR AND SHALL BE MAINTAINED
 SELF-CLOSING OR SHALL BE AUTOMATIC CLOSING BY ACTUATION
 OF A SMOKE DETECTOR. ALL OTHER OPENINGS SHALL BE FIRE
 PROTECTED IN AN APPROVED MANNER. EXISTING FUSIBLE
 LINK-TYPE AUTOMATIC DOOR-CLOSING DEVICES SHALL BE
 PERMITTED IN ALL SHAFTS EXCEPT STAIRWAYS IF THE FUSIBLE
 LINK RATING DOES NOT EXCEED 135?F (57?C).
  
 7B) SHEET LS-2 THE NORTHWEST STAIRWELLDOES NOT INDICATE
 THIS IS A FIRE RATED WALL. EXST BLDG CODE 703.2.3
 SUPPLEMENTAL STAIRWAY ENCLOSURE REQUIREMENTS. WHERE THE
 WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR
 AREA, STAIRWAYS THAT ARE PART OF THE MEANS OF EGRESS
 SERVING THE WORK AREA SHALL, AT A MINIMUM, BE ENCLOSED
 WITH SMOKE-TIGHT CONSTRUCTION ON THE HIGHEST WORK AREA
 FLOOR AND ALL FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
  
 2010 EXST BLDG CODE 912.7.2 STAIRWAYS. WHEN A CHANGE OF
 OCCUPANCY CLASSIFICIATION IS MADE TO A HIGHER HAZARD
 CATEGORY AS SHOWN IN TABLE 912.4, INTERIOR STAIRWAYS
 SHALL BE ENCLOSED AS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING.
  
 7C) DOORS THAT ARE REQUIRED TO BE RATED FOR STAIRWELLS,
 VERTICAL LULA LIFTS FOR THE 2ND & 3RD FLOOR ARE NOT
 LOCATED ON THE DOOR SHCEDULE FOUND ON SHEET A6. 2010
 FBC-B OPENING PROTECTIVES, TABLE 715.4.
  
 8) SECTION 904 FIRE PROTECTION 904.1 GENERAL. FIRE
 PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED, THE COVER SHEET INDICATES THIS TO BE A
 FULLY SPRINKLERED BUILDING.
  
 9) SECTION 905 MEANS OF EGRESS. 905.1 GENERAL.
 MEANS OF EGRESS IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 SECTION 912.
 EXST BLDG CODE912.4.1 MEANS OF EGRESS FOR CHANGE TO
 HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 THE STAIRWELLS WILL NEED TO PROVIDE HANRAILS ON BOTH
 SIDES OF THE STAIRS IN COMPLIANCE WITH 1012.1-9 &
 GAURDRAILS WHEN THERE IS NO WALLS INCOMPLIANCE WITH
 1013.1-3.
  
 10) PLEASE PROVIDE THE MANUFACTURERS SPEC FOR THE LULA
 LIFT INDICATING COMPLIANCE WITH 2010 ACCESSIBILITY CODE
 410.1 ASME A18.1. 2010 EXST BLDG CODE SECTION 906
 ACCESSIBILITY 906.1 ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
 2010 EXST BLDG CODE 912.8 ACCESSIBILITY. EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 2010 ACCESSIBILTY CODE (FL GRAY BOX) 201.1.1 VERTICAL
 ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 SEE EXCEPTIONS.
 BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN.
  
 2010 ACCESSIBILITY CODE.202.4 ALTERATIONS AFFECTING
 PRIMARY FUNCTION AREAS.
 IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION
 THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS
 TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE,
 THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE
 REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING
 THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE
 BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH
 ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL
 ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1.
 ALTERATIONS TO WINDOWS, HARDWARE, CONTROLS, ELECTRICAL
 OUTLETS, AND SIGNAGE SHALL NOT BE DEEMED TO BE
 ALTERATIONS THAT AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 11) LS-3 THE SOUTH STAIRWELL INDICATES THE LULA LIFT
 WITHIN THE NEW STAIR ENCLOSURE. 2010 FBC-B 1022.4
 REQUIRED PENETRATIONS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-11 Cont ID  
Sent By jwitmer Date 2013-01-11 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2013-01-10 Time 13:55 Sent To  
Notes
2013-01-10 14:11:35BUILDING PLAN REVIEW
 PERMIT: 13010089
 ADD: 2119 S DIXIE HWY
 CONT: SOUTHEAST CONSTRUCTION.
 TEL: (954)394-3991
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 JAN. 11/2013
 1ST REVIEW
 ACTION: DENIED
  
 1) NOTE: SHEET SP-1 INDICATES THIS PROJECT CONSIST OF A
 LEVEL 2 ALTERATION. PLEASE UPDATE THE PERMIT
 APPLICATION AS WELL AS SP-1 TO INDICATE THIS PROJECT IS
 CONSIDERED A CHANGE OF OCCUPANCY SINCE IT IS A CHANGE
 OF USE FROM A AUTOMOBLIE DEALERSHIP MIXED USE SERVICE
 DEPARTMENT, STORAGEAND THE CAR SHOWROOM, SALES OFFICES
 BEING MERCANTILE. THE LAST RECORDED USE WAS RAGTOPS A
 AUTOMOBILE DEALERSHIP. A BUSINESS CAME IN AND RECEIVED
 A BUSINESS TAX LICENSE KIRKLAND EVENTS DESTINATION
 SERVICES BUT NEVER CAME IN FOR A CHANGE IN OCCUPANCY
 WHICH WOULD HAVE CREATED A MIXED USE BUILDING.
  
 2) SHEET SP-1 THE DESIGNER OF RECORD HAS NOT INDICATED
 IF THE PROPOSED DESIGN IS:
 2A) 2010 EXISTING BUILDING CODE 912.1.1.1 CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION.
 OR
 2B) 2010 EXISTING BUILDING CODE 912.1.1.2 CHANGE OF
 OCCUPANCY CLASSIFICATION WITH SEPARATION.
  
 3) SHEET SP-1 THE WIND DESIGN CRITERIA INDICATES THE
 DESIGN TO ASCE 7-10 THE CURRENT WIND DESIGN BUT THE
 WRONG WIND SPEED FOR A CATEGORY II BUILDING PLEASE SEE
 2010 FBC-B FIGURE 1609A VULT 170 MPH.
  
 4A) SHEET SP-1, OCCUPANT LOAD CHART, FIRST FLOOR THE
 RETAIL LOUNGE, RETAIL BOUTIQUE & COFFEE SHOP ALL LIST
 60 SQ FT PER OCCUPANT PLEASE REVIEW 2010 FBC-B TABLE
 1004.1.1 FOR MERCANTILE GRADE FLOOR AT 30 SQ FT/
 OCCUPANT.
  
 4B) SHEET SP-1 INDICATES A NEW DINING AREA BUT THE
 PLANS DO NOT INDICATE THE USE OF A KITCHEN AND DISH
 WASHING AREA, PLEASE BE AWARE OF 2010 EXST BLDG CODE
 SECTION
 910.3 INTERCEPTOR REQUIRED. IF THE NEW OCCUPANCY WILL
 PRODUCE GREASE OR OIL-LADEN WASTES, INTERCEPTORS SHALL
 BE PROVIDED AS REQUIRED IN THE FLORIDA BUILDING CODE,
 PLUMBING.
  
 5) SHEET SP-1 LIFE SAFETY PLAN, PLEASE PROVIDE THE
 FURNATURE LAYOUT FOR MEANS OF EGRESS, AACCESSIBLE PATH
 OF TRAVEL ... EXST BLDG CODE 905.1.
  
 6) SHEET SP-1 LIFE SAFETY PLAN, PLEASE PROVIDE THE
 INTENDED USE FOR THE LOBBY AREA THE OCCUPANT LOAD OF
 100 SQ FT PER OCCUPANT DOES NOT DECLARE TYPE OF USAGE
 PROVIDED SUCH AS MERCANTILE, STORAGE ... 2010 FBC-B.
 302.1 STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED BELOW. A ROOM OR SPACE THAT IS
 INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
 STRUCTURES WITH MULTIPLE OCCUPANCIES OR USES SHALL
 COMPLY WITH SECTION 508. WHERE A STRUCTURE IS PROPOSED
 FOR A PURPOSE THAT IS NOT SPECIFICALLY PROVIDED FOR IN
 THIS CODE, SUCH STRUCTURE SHALL BE CLASSIFIED IN THE
 GROUP THAT THE OCCUPANCY MOST NEARLY RESEMBLES,
 ACCORDING TO THE FIRE SAFETY AND RELATIVE HAZARD
 INVOLVED.
  
 7A) SHEET SP-1 FREIGHT ELEVATOR. 2010 EXISTING BUILDING
 CODE IN EITHER CASE IF THE DESIGNER OF RECORD CHOICES
 912.1.1.1 OR 912.1.1.2 SEPERATED OR NON-SEPERATED USE
 BOTH CODE SECTIONS REFER YOU BACK TO CHAPTER 8 FOR THE
 NEW OCCUPANCY CLASSIFICATION IN THE BUILDING AND THE
 REQUIREMENTS OF THIS CHAPTER. THE PROVISIONS
 ESSENTIALLY CLASSIFY CHANGES OF OCCUPANCY
 CLASSIFICATION AS LEVEL 3 ALTERATIONS. BY DIRECTLY
 STATING THE REQUIEMENTS OF CHAPTER 8 SHALL OVERRIDES
 THE REQUIREMENT FOR THE RECONFIGURATION OR ALTERATION
 TO BE OCCURRING IN THE 50 PER CENT OR MORE OF THE TOTAL
 BUILDING. THE APPLICATION OF CHAPTER 8 IN TURN REQUIRES
 COMPLIANCE WITH CHAPTERS 6 & 7 AS STATED IN SECTION
 801.2.
 2010 EXST BLDG CODE 703.2.1 EXISTING VERTICAL OPENINGS.
 ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO
 OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE
 SECTIONS OF THE FLORIDA FIRE PREVENTION CODE.
 2010 EXST BLDG CODE 912.7 ENCLOSURE OF VERTICAL SHAFTS.
 ENCLOSURE OF VERTICAL SHAFTS SHALL BE IN ACCORDANCE
 WITH SECTIONS 912.7.1 THROUGH 912.7.4.
 2010 EXST BLDG CODE 912.7.3 OTHER VERTICAL SHAFTS.
 INTERIOR VERTICAL SHAFTS OTHER THAN STAIRWAYS,
 INCLUDING BUT NOT LIMITED TO ELEVATOR HOISTWAYS AND
 SERVICE AND UTILITY SHAFTS, SHALL BE ENCLOSED AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING WHEN
 THERE IS A CHANGE OF USE TO A HIGHER HAZARD CATEGORY AS
 SPECIFIED IN TABLE 912.4.
  
 2010 EXST BLDG CODE 912.7.4 OPENINGS. ALL OPENINGS INTO
 EXISTING VERTICAL SHAFT ENCLOSURES SHALL BE PROTECTED
 BY FIRE ASSEMBLIES HAVING A FIRE-PROTECTION RATING OF
 NOT LESS THAN 1 HOUR AND SHALL BE MAINTAINED
 SELF-CLOSING OR SHALL BE AUTOMATIC CLOSING BY ACTUATION
 OF A SMOKE DETECTOR. ALL OTHER OPENINGS SHALL BE FIRE
 PROTECTED IN AN APPROVED MANNER. EXISTING FUSIBLE
 LINK-TYPE AUTOMATIC DOOR-CLOSING DEVICES SHALL BE
 PERMITTED IN ALL SHAFTS EXCEPT STAIRWAYS IF THE FUSIBLE
 LINK RATING DOES NOT EXCEED 135?F (57?C).
  
 7B) SHEET SP-1 OPEN STAIRWELLS. EXST BLDG CODE 703.2.3
 SUPPLEMENTAL STAIRWAY ENCLOSURE REQUIREMENTS. WHERE THE
 WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR
 AREA, STAIRWAYS THAT ARE PART OF THE MEANS OF EGRESS
 SERVING THE WORK AREA SHALL, AT A MINIMUM, BE ENCLOSED
 WITH SMOKE-TIGHT CONSTRUCTION ON THE HIGHEST WORK AREA
 FLOOR AND ALL FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
  
 2010 EXST BLDG CODE 912.7.2 STAIRWAYS. WHEN A CHANGE OF
 OCCUPANCY CLASSIFICIATION IS MADE TO A HIGHER HAZARD
 CATEGORY AS SHOWN IN TABLE 912.4, INTERIOR STAIRWAYS
 SHALL BE ENCLOSED AS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING.
 EXCEPTIONS:
 1. IN OTHER THAN GROUP I OCCUPANCIES, AN ENCLOSURE
 SHALL NOT BE REQUIRED FOR OPENINGS SERVING ONLY ONE
 ADJACENT FLOOR AND THAT ARE NOT CONNECTED WITH
 CORRIDORS OR STAIRWAYS SERVING OTHER FLOORS.
 2. UNENCLOSED EXISTING STAIRWAYS NEED NOT BE ENCLOSED
 IN A CONTINUOUS VERTICAL SHAFT IF EACH STORY IS
 SEPARATED FROM OTHER STORIES BY 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION OR APPROVED WIRED
 GLASS SET IN STEEL FRAMES AND ALL EXIT CORRIDORS ARE
 SPRINKLERED. AN OPENING BETWEEN THE CORRIDOR AND THE
 OCCUPANT SPACE SHALL HAVE AT LEAST ONE SPRINKLER HEAD
 ABOVE THE OPENINGS ON THE TENANT SIDE. THE SPRINKLER
 SYSTEM SHALL BE PERMITTED TO BE SUPPLIED FROM THE
 DOMESTIC WATER-SUPPLY SYSTEMS, PROVIDED THE SYSTEM IS
 OF ADEQUATE PRESSURE, CAPACITY, AND SIZING FOR THE
 COMBINED DOMESTIC AND SPRINKLER REQUIREMENTS.
  
  
 NOTE: 2010 EXST BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
  
 8) SECTION 904 FIRE PROTECTION 904.1 GENERAL. FIRE
 PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED, THE COVER SHEET INDICATES THIS TO BE A
 FULLY SPRINKLERED BUILDING.
  
 9) SECTION 905 MEANS OF EGRESS. 905.1 GENERAL.
 MEANS OF EGRESS IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 SECTION 912.
 EXST BLDG CODE912.4.1 MEANS OF EGRESS FOR CHANGE TO
 HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 10) 2010 EXST BLDG CODE SECTION 906 ACCESSIBILITY 906.1
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 2010 EXST BLDG CODE 912.8 ACCESSIBILITY. EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 2010 ACCESSIBILTY CODE (FL GRAY BOX) 201.1.1 VERTICAL
 ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 SEE EXCEPTIONS.
 BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN.
  
 2010 ACCESSIBILITY CODE.202.4 ALTERATIONS AFFECTING
 PRIMARY FUNCTION AREAS.
 IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION
 THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS
 TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE,
 THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE
 REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING
 THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE
 BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH
 ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL
 ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1.
 ALTERATIONS TO WINDOWS, HARDWARE, CONTROLS, ELECTRICAL
 OUTLETS, AND SIGNAGE SHALL NOT BE DEEMED TO BE
 ALTERATIONS THAT AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 NOTE THIS REVIEW IS STOPPED BECAUSE OF EXCESSIVE CODE
 VIOLATION!!!!! A THOROUGH REVIEW CAN NOT BE MADE AT
 THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION
 REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT
 PART OF THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2013-08-16 Cont ID  
Sent By dharvey Date 2013-08-16 Time 14:53 Rev Time 0.00
Received By dharvey Date 2013-08-16 Time 14:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-08-01 Cont ID  
Sent By dharvey Date 2013-08-01 Time 16:11 Rev Time 0.00
Received By dharvey Date 2013-08-01 Time 16:09 Sent To  
Notes
2013-08-01 16:11:48PREVIOUSLY SIGNED OFF. NO REVIEW NEEDED
2013-07-11 10:26:23NEW SHEETS SUBMITTED. JG.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-20 Cont ID  
Sent By DHARVEY Date 2013-05-20 Time 15:30 Rev Time 0.00
Received By dharvey Date 2013-05-20 Time 15:30 Sent To  
Notes
2013-05-20 15:30:525-20-13
 CORRECTIONS MADE - VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-09 Cont ID  
Sent By rlecky Date 2013-01-09 Time 09:14 Rev Time 0.00
Received By rlecky Date 2013-01-08 Time 13:03 Sent To  
Notes
2013-01-09 09:18:5213010089
 2119 S. DIXIE HIGHWAY
 INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE
 EQUIPMENT AND PANEL BOARDS. VERIFY THE EQUIPMENT FAULT
 CURRENT RATING IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE
 FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION, HIGH-LEG MARKING, AND THE ELECTRICAL
 SERVICE EQUIPMENT AND DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE PANEL BOARD SCHEDULES SHOWING BALANCED LOADS.
 INCLUDE A SUMMARY LOAD CALCULATION FOR THE SERVICE
 EQUIPMENT. NEC 210.3, 215.2, 220.40, 408.4
  
 VERIFY SAFETY CLEARANCES HAVE BEEN OBSERVED FOR PANEL
 ?C?. NEC 215.5, 110.26
  
 PROVIDE DEDICATED 20 AMPERE BRANCH CIRCUIT (S) FOR
 SIGNAGE. NEC 600.5
  
 RECEPTACLE OUTLETS ARE REQUIRED FOR SHOW WINDOWS. NEC
 210.62, 220.14, 220.40, 220.43
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2013-08-17 Cont ID  
Sent By wjolin Date 2013-08-17 Time 17:41 Rev Time 0.00
Received By wjolin Date 2013-08-17 Time 17:35 Sent To  
Notes
2013-08-17 17:41:282119 SOUTH DIXIE HIGHWAY
 PERMIT #13010089
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-2: THE EXISTING HVAC ROOM IS INDICATED AS BEING
 A STORAGE ROOM. PER NFPA 1 SECTION 10.19.5.1,
 COMBUSTIBLE MATERIAL SHALL NOT BE STORED IN MECHANICAL
 ROOMS OR ELECTRICAL ROOMS.
  
 AS A NON-SEPARTED MIXED USE BUILDING, THE MOST STRIGENT
 LIFE SAFETY ITEMS PER OCCUPANCY WILL BE APPLICABLE.
 THEREFORE, PER NFPA 101 SECTION 38.3.4.1 A FIRE ALARM
 SYSTEM SHALL BE PROVIDED WHERE THE BUILDING IS THREE OR
 MORE STORIES IN HEIGHT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 SPRINKLER DRAWINGS: DRAWINGS REQUIRE ENGINEER'S
 SIGN/SEAL. FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY
 AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA
 72.
  
 SPRINKLER DRAWINGS: INDICATE THE SYSTEM IMPROVEMENTS
 THAT WILL BE IMPLEMENTED TO BRING THE EXISTING PIPE
 SCHEDULE INTO COMPLIANCE WITH NFPA 13. NOTE: PER NFPA
 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE BEEN IN
 SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR
 REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS
 SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT
 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION,
 SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED
 TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION FOR FIELD SERVICE TESTING.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
2013-08-07 16:14:47NEW SHEETS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-07-26 Cont ID  
Sent By wjolin Date 2013-07-26 Time 10:47 Rev Time 0.00
Received By wjolin Date 2013-07-25 Time 10:45 Sent To  
Notes
2013-07-26 10:46:192119 SOUTH DIXIE HIGHWAY
 PERMIT #13010089
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-2: THE EXISTING HVAC ROOM IS INDICATED AS BEING
 A STORAGE ROOM. PER NFPA 1 SECTION 10.19.5.1,
 COMBUSTIBLE MATERIAL SHALL NOT BE STORED IN MECHANICAL
 ROOMS OR ELECTRICAL ROOMS.
  
 AS A NON-SEPARTED MIXED USE BUILDING, THE MOST STRIGENT
 LIFE SAFETY ITEMS PER OCCUPANCY WILL BE APPLICABLE.
 THEREFORE, PER NFPA 101 SECTION 38.3.4.1 A FIRE ALARM
 SYSTEM SHALL BE PROVIDED WHERE THE BUILDING IS THREE OR
 MORE STORIES IN HEIGHT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 SPRINKLER DRAWINGS: DRAWINGS REQUIRE ENGINEER'S
 SIGN/SEAL. FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY
 AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA
 72.
  
 SPRINKLER DRAWINGS: INDICATE THE SYSTEM IMPROVEMENTS
 THAT WILL BE IMPLEMENTED TO BRING THE EXISTING PIPE
 SCHEDULE INTO COMPLIANCE WITH NFPA 13. NOTE: PER NFPA
 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE BEEN IN
 SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR
 REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS
 SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT
 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION,
 SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED
 TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION FOR FIELD SERVICE TESTING.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-05-18 Cont ID  
Sent By WJOLIN Date 2013-05-18 Time 16:10 Rev Time 0.00
Received By wjolin Date 2013-05-16 Time 13:44 Sent To  
Notes
2013-05-16 15:17:372119 SOUTH DIXIE HIGHWAY
 PERMIT #13010089
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE
 STAIR. HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF
 NOT LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES.
  
 SHEET LS-1: STAIR ENCLOSURE DOOR #10 OBSTRUCTS THE
 EGRESS PATH OF OCCUPANTS UTILIZING DOOR #11.
  
 SHEET A-4: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESS VISIBLE FROM THE STREET ON EAST
 ELEVATION. NUMBERS SHALL BE ATTACHED TO THE BUILDING
 AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE
 AND SHALL CONTRAST THE BACKGROUND.
  
 SPRINKLER DRAWINGS: DRAWINGS REQUIRE ENGINEER'S
 SIGN/SEAL. FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY
 AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA
 72.
  
 SPRINKLER DRAWINGS: INDICATE THE SYSTEM IMPROVEMENTS
 THAT WILL BE IMPLEMENTED TO BRING THE EXISTING PIPE
 SCHEDULE INTO COMPLIANCE WITH NFPA 13. NOTE: PER NFPA
 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE BEEN IN
 SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR
 REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS
 SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT
 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION,
 SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED
 TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION FOR FIELD SERVICE TESTING.
  
 ELECTRICAL DRAWINGS: PROVIDE ENGINEERED LAYOUT OF
 ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING.
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1-1/2 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-01-14 Cont ID  
Sent By wjolin Date 2013-01-14 Time 14:20 Rev Time 0.00
Received By wjolin Date 2013-01-14 Time 13:23 Sent To  
Notes
2013-01-14 14:20:142119 SOUTH DIXIE HIGHWAY
 PERMIT #13010089
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 OTHER THAN THE COVER SHEET, THE PROJECT ADDRESS IS
 INCORRECTLY INDICATED AS 2199 SOUTH DIXIE HIGHWAY.
  
 PROVIDE A LIFE SAFETY PLANS INDICATING FURNITURE
 LAYOUTS, NEW/EXISTING HOURLY FIRE BARRIER RATINGS,
 EMERGENCY LIGHTING, COMMON PATH OF TRAVEL ETC.
  
 EXIT DISCHARGE,STAIRS AND EGRESS COMPONENTS SHALL
 CONFORM TO THE LIFE SAFETY REQUIREMENTS OF CHAPTER 7 OF
 NFPA 101 FLORIDA 2007 EDITION. TOO MANY VIOLATIONS TO
 LIST.
  
 OCCUPANT LOAD FACTORS SHALL COMPLY WITH TABLE 7.3.1.2
 OF THE FFPC. SEVERAL OCCUPANT LOAD FACTORS ARE
 INCORRECT SUCH AS 60 SQ.FT. PER PERSON FOR MERCANTILE
 ON STREET FLOOR. A CONFERENCE ROOM WOULD BE FIGURED AT
 15 SQ.FT. PER PERSON AS THE USAGE IS ASSEMBLY.
  
 THE SECOND FLOOR INDICATES WORK TABLES; PLEASE INDICATE
 HOW THIS SPACE WILL BE USED.
  
 THE THIRD FLOOR INDICATES SEVERAL DISPLAY CASES SO A
 STORAGE OCCUPANCY IS NOT APPROPRIATE FOR THIS USAGE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ? NFPA 101
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE
 SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE ? NFPA
 101
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 TOO MANY CODE VIOLATIONS EXIST ON THE PLANS AT THIS
 TIME TO PERFORM A THOROUGH AND COMPLETE PLAN REVIEW.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-01-16 Cont ID  
Sent By fmittner Date 2013-01-16 Time 16:58 Rev Time 0.00
Received By fmittner Date 2013-01-16 Time 16:58 Sent To  
Notes
2013-01-17 08:48:14B-4
2013-01-16 16:59:07APPROVED FOR INTERIOR WORK ONLY. ANY DOOR MODIFICATIONS
 REQUIRE A COA. QUESTIONS CONTACT FRIEDERIKE 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-10-08 Cont ID  
Sent By rmcdouga Date 2013-10-08 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2013-10-03 Time 08:20 Sent To  
Notes
2013-10-05 08:21:39PROCESSED PLANS OUT. (IMPACT FEE STAMPED PLANS)

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-08-19 Cont ID  
Sent By jwitmer Date 2013-08-19 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2013-08-07 Time 16:18 Sent To  
Notes
2013-08-07 16:19:21SENT TO B43 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-02 Cont ID  
Sent By lwagner Date 2013-08-02 Time 09:07 Rev Time 0.00
Received By lwagner Date 2013-07-10 Time 10:29 Sent To  
Notes
2013-07-11 10:30:09SENT TO B25 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-28 Cont ID  
Sent By jwitmer Date 2013-05-28 Time 10:19 Rev Time 0.00
Received By lwagner Date 2013-05-09 Time 10:32 Sent To  
Notes
2013-05-10 10:36:13B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-06 Cont ID  
Sent By jwitmer Date 2013-01-16 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2013-01-04 Time 13:57 Sent To  
Notes
2013-01-07 13:59:01B--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2013-10-08 Cont ID  
Sent By rmcdouga Date 2013-10-08 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2013-10-08 Time 09:43 Sent To  
Notes
2013-10-08 09:45:10MU-2013-021291

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2013-08-17 Cont ID  
Sent By jwitmer Date 2013-08-17 Time 11:43 Rev Time 0.00
Received By jwitmer Date 2013-08-17 Time 11:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-07-20 Cont ID  
Sent By jwitmer Date 2013-07-20 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2013-07-20 Time 13:45 Sent To  
Notes
2013-07-20 13:46:52BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-05-21 Cont ID  
Sent By jwitmer Date 2013-05-21 Time 15:27 Rev Time 0.00
Received By jwitmer Date 2013-05-21 Time 15:27 Sent To  
Notes
2013-05-21 15:28:01BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-01-11 Cont ID  
Sent By jwitmer Date 2013-01-11 Time 09:49 Rev Time 0.00
Received By jwitmer Date 2013-01-11 Time 09:49 Sent To  
Notes
2013-01-11 09:49:04BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2013-08-15 Cont ID  
Sent By lwagner Date 2013-08-15 Time 12:09 Rev Time 0.00
Received By lwagner Date 2013-08-15 Time 12:03 Sent To  
Notes
2013-08-15 12:12:41PER LETTER FROM THE ARCHITECT THE PLUMBING CONTRACTOR
 WILL BE REQUIRED TO SUBMIT A DRAWING WITH THE
 APPLICATION FOR PLUMBING PERMIT.

Review Stop P PLUMBING
Rev No 3 Status F Date 2013-08-02 Cont ID  
Sent By lwagner Date 2013-08-02 Time 09:05 Rev Time 0.00
Received By lwagner Date 2013-07-29 Time 14:36 Sent To  
Notes
2013-08-02 09:05:36FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #3
 DENIED:
  
 1. SHEET A 1 SHOWS RECONFIGURED RESTROOMS AND A NEW
 HI/LO DRINKING FOUNTAIN. A 2 SHOWS NEW LOUNGE SINK AND
 DRINKING FOUNTAIN. A3 SHOWS RECONFIGURED RESTROOMS. NO
 PLUMBING PLANS WERE INCLUDED WITH THIS SET OF DRAWINGS.
 FBC 2010 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. 107.3.5.1.3 PLUMBING:
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 13. PLUMBING RISER
  
 ***NOTE***
 1. A PLUMBING CONTRACTOR COULD SUPPLY SEPARATE
 DRAWINGS, APPLICATION, ANND PERRIT FOR THIS PROJECT.
 2. THE DEPARTMENT OF HOTELS AND RESTAURANTS HAVE PLAN
 REVIEW REQUIREMENTS OTHER THAN THE FLORIDA PLUMBING
 CODE SUCH AS HAND SINKS, THREE COMPARTMENT SINKS, ETC.
 FBC PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES:
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805?6692
 EMAIL [email protected]
 FAX # 805?6676
 ???????????????????????????????????????????????????????
 ????????????????????????

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-07-16 Cont ID  
Sent By lwagner Date 2013-07-16 Time 14:32 Rev Time 0.00
Received By lwagner Date 2013-07-16 Time 13:06 Sent To  
Notes
2013-07-16 13:45:53FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 1. SHEET A 1 SHOWS RECONFIGURED RESTROOMS AND A NEW
 HI/LO DRINKING FOUNTAIN. A 2 SHOWS NEW LOUNGE SINK AND
 DRINKING FOUNTAIN. A3 SHOWS RECONFIGURED RESTROOMS. NO
 PLUMBING PLANS WERE INCLUDED WITH THIS SET OF DRAWINGS.
 FBC 2010 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. 107.3.5.1.3 PLUMBING:
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 13. PLUMBING RISER
  
 ***NOTE***
  
 1. A PLUMBING CONTRACTOR COULD SUPPLY SEPARATE
 DRAWINGS, APPLICATION, ANND PERRIT FOR THIS PROJECT.
  
 2. THE DEPARTMENT OF HOTELS AND RESTAURANTS HAVE PLAN
 REVIEW REQUIREMENTS OTHER THAN THE FLORIDA PLUMBING
 CODE SUCH AS HAND SINKS, THREE COMPARTMENT SINKS, ETC.
 FBC PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES:
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-05-28 Cont ID  
Sent By lwagner Date 2013-05-28 Time 10:19 Rev Time 0.00
Received By lwagner Date 2013-05-28 Time 08:58 Sent To  
Notes
2013-05-28 10:19:28FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A 1 SHOWS RECONFIGURED RESTROOMS AND A NEW
 HI/LO DRINKING FOUNTAIN. A 2 SHOWS NEW LOUNGE SINK AND
 DRINKING FOUNTAIN. A3 SHOWS RECONFIGURED RESTROOMS. NO
 PLUMBING PLANS WERE INCLUDED WITH THIS SET OF DRAWINGS.
 FBC 2010 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. 107.3.5.1.3 PLUMBING:
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 13. PLUMBING RISER
  
 2. FBC PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES:
 A-2 RESTAURANTS - ONE SERVICE SINK IS REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-01-16 Cont ID  
Sent By fmitter Date 2013-01-16 Time 16:56 Rev Time 0.00
Received By fmittner Date 2013-01-16 Time 16:56 Sent To  
Notes
2013-01-16 16:58:20VALUE DOES NOT EXCEED 50%. PASSED WITH CONDITIONS THAT
 LANDSCAPING AND PARKING BE ADDRESSED/MET PRIOR TO CO.
 QUESTIONS CONTACT FRIEDERIKE 822-1457.