Inspection Details
INSPECTION DETAILS FOR PERMIT 17110075
Permit Number 17110075 Owner Name WEST PALM FCH APARTMENTS LLC
Permit Type BLD-COM Permit Address 290 N OLIVE AVE
Inspection Type FIRE FINAL-9 City WEST PALM BEACH
Inspect Area   Inspector 7475
Request Date 2020-03-12 Scheduled Date 2020-03-13
Instructions NEED OK TCO FL 3 & 5 EXC 521-524 & 540
Contract Info  
Contractor CGC055839 Inspect Date 2020-03-13 09:00
Result F Fail Code  
Comments SEE NOTES
Work Time   Confirm 530349
Fee ID  
Inspector Notes
Date Text
2020-03-13 13:20:40PERMIT #17110075 - INSPECTION FAILED.
 NOT OK FOR TCO. HERE ARE SOME OF THE
 CONCERNS THAT WE HAVE:
  
 1. THE STAIRWELL PRESSURIZATION HAS NOT
 BEEN DONE.
 2. THE FIRE ALARM ON FLOORS 6 - 10 HAS
 NOT BEEN TESTED.
 3. THE FIRE ALARM SYSTEM IS ON TEST
 DURING THE DAY. THEREFORE, IF THERE IS A
 TRUE INCIDENT IN THE BUILDING THE FIRE
 DEPARTMENT WILL NOT BE DISPATCHED.
 4. THE FIRE ALARM IS BEING DISABLED IN
 THE SPINA SPACE AND LOBBY DURING THE DAY
 DURING TESTING.
 5. DRYWALL THAT IS NOT RATED HAS BEEN
 INSTALLED IN THE EGRESS CORRIDORS.
 6. SHAFT WALL IN STAIRWELL IS NOT
 COMPLETE.
  
 TRAVIS TELFAIR
 7475