INSPECTION DETAILS FOR PERMIT 17110075 |
Permit Number |
17110075 |
Owner Name |
WEST PALM FCH APARTMENTS LLC |
Permit Type |
BLD-COM |
Permit Address |
290 N OLIVE AVE |
Inspection Type |
FIRE FINAL-9 |
City |
WEST PALM BEACH |
Inspect Area |
|
Inspector |
7475 |
Request Date |
2020-03-12 |
Scheduled Date |
2020-03-13 |
Instructions |
NEED OK TCO FL 3 & 5 EXC 521-524 & 540 |
Contract Info |
|
Contractor |
CGC055839 |
Inspect Date |
2020-03-13 09:00 |
Result |
F |
Fail Code |
|
Comments |
SEE NOTES |
Work Time |
|
Confirm |
530349 |
Fee ID |
|
|
Inspector Notes |
Date |
Text |
2020-03-13 13:20:40 | PERMIT #17110075 - INSPECTION FAILED. | | NOT OK FOR TCO. HERE ARE SOME OF THE | | CONCERNS THAT WE HAVE: | | | | 1. THE STAIRWELL PRESSURIZATION HAS NOT | | BEEN DONE. | | 2. THE FIRE ALARM ON FLOORS 6 - 10 HAS | | NOT BEEN TESTED. | | 3. THE FIRE ALARM SYSTEM IS ON TEST | | DURING THE DAY. THEREFORE, IF THERE IS A | | TRUE INCIDENT IN THE BUILDING THE FIRE | | DEPARTMENT WILL NOT BE DISPATCHED. | | 4. THE FIRE ALARM IS BEING DISABLED IN | | THE SPINA SPACE AND LOBBY DURING THE DAY | | DURING TESTING. | | 5. DRYWALL THAT IS NOT RATED HAS BEEN | | INSTALLED IN THE EGRESS CORRIDORS. | | 6. SHAFT WALL IN STAIRWELL IS NOT | | COMPLETE. | | | | TRAVIS TELFAIR | | 7475 |
|