INSPECTION DETAILS FOR PERMIT 17110075 |
Permit Number |
17110075 |
Owner Name |
WEST PALM FCH APARTMENTS LLC |
Permit Type |
BLD-COM |
Permit Address |
290 N OLIVE AVE |
Inspection Type |
FIRE FINAL-8 |
City |
WEST PALM BEACH |
Inspect Area |
|
Inspector |
7475 |
Request Date |
2020-03-11 |
Scheduled Date |
2020-03-12 |
Instructions |
NEED OK TCO FL 3 & 5 EXC 521-524 & 540 |
Contract Info |
|
Contractor |
CGC055839 |
Inspect Date |
2020-03-12 11:45 |
Result |
F |
Fail Code |
|
Comments |
SEE NOTES |
Work Time |
|
Confirm |
530245 |
Fee ID |
|
|
Inspector Notes |
Date |
Text |
2020-03-12 12:43:55 | PERMIT #17110075 - INSPECTION FAILED. | | NOT OK FOR TCO. HERE ARE SOME THE | | CONCERNS THAT WE HAVE: | | | | 1. THE STAIRWELL PRESSURIZATION HAS NOT | | BEEN DONE. | | 2. THE FIRE ALARM ON FLOORS 6 - 10 IS | | NOT COMPLETE. | | 3. THE FIRE ALARM SYSTEM IS ON TEST | | DURING THE DAY. THEREFORE, IF THERE IS A | | TRUE INCIDENT IN THE BUILDING THE FIRE | | DEPARTMENT WILL NOT BE DISPATCHED. | | 4. THE FIRE ALARM IS BEING DISABLED IN | | THE SPINA SPACE AND LOBBY DURING THE DAY | | DURING TESTING. | | 5. DRYWALL THAT IS NOT RATED IS BEING | | INSTALLED IN THE STAIRWELLS AND/OR | | EGRESS CORRIDORS. | | 6. DUE TO THE DRYWALL BEING INSTALLED IN | | THE STAIRWELL, THE DISTANCE BETWEEN THE | | WALL AND THE HANDRAIL IS ONLY 2 INCHES. | | | | TRAVIS TELFAIR | | 7475 |
|