2020-01-02 14:14:47 | 603.3MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR |
| COUNTERTOPS SHALL BE INSTALLED WITH THE |
| BOTTOM EDGE OF THE REFLECTING SURFACE 40 |
| INCHES (1015 MM) MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. MIRRORS NOT |
| LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 35 INCHES (890 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 306.3.1GENERAL. |
| SPACE UNDER AN ELEMENT BETWEEN 9 INCHES |
| (230 MM) AND 27 INCHES (685 MM) ABOVE |
| THE FINISH FLOOR OR GROUND SHALL BE |
| CONSIDERED KNEE CLEARANCE AND SHALL |
| COMPLY WITH 306.3. |
| WOMENS ACCESSIBLE RESTROOM WOODEN VANITY |
| LEG SHALL BE REMOVED AND CAULK |
| COUNTERTOP TO WALL |
| |
| ALL APPLIANCES SHALL BE INSTALLED AND |
| CONNECTED FOR FINAL PLUMBING INSPECTION |
| |
| ELIMINATE DRINKING FOUNTAIN DRAIN LINE |
| IN HALLWAY |
| |
| SIGNAGE REQUIRED FBC 2017 BUILDING |
| [P]2902.4 SIGNAGE. |
| REQUIRED PUBLIC FACILITIES SHALL BE |
| PROVIDED WITH SIGNS THAT DESIGNATE THE |
| SEX AS REQUIRED BY SECTION 2902.2. SIGNS |
| SHALL BE READILY VISIBLE AND LOCATED |
| NEAR THE ENTRANCE TO EACH TOILET |
| FACILITY. SIGNS FOR ACCESSIBLE TOILET |
| FACILITIES SHALL COMPLY WITH THE FLORIDA |
| BUILDING CODE, ACCESSIBILITY. |
| |
| FIRE CAULK MISSING ON COPPER WATER |
| SERVICE LINE WHERE ENTERING THE UNIT |
| |
| ALL CLEAN OUTS IN WALL SHALL BE |
| ACCESSIBLE AND CLEAN OUT COVERS SHALL BE |
| INSTALLED FOR FINAL |
| |
| |
| |
| |